| 2018-07-11 05:36:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NO ELECTRICAL WORK SHOWN ON SUBMITTED PLAN. NOTE #5 |
| | IN "SCOPE OF WORK" STATES NEW SWITCHES, RECEPTACLES, |
| | SENSORS, ETC WILL BE INSTALLED. PROVIDE ELECTRICAL PLAN |
| | FOR REVIEW, SIGNED AND SEALED BY A LICENSED DESIGN |
| | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. IF |
| | THERE IS NOT ANY ELECTRICAL WORK INCLUDED WITH THIS |
| | PERMIT, STATE THAT ON PLAN. FS 471.003(2)(H); 471.025; |
| | WPB FBC 107.2.1, 107.3.5 |
| | |
| | 2, PLANS PREPARED BY AN ENGINEER MUST BE SIGNED AND |
| | SEALED. PE ONLY SIGNED PLANS. ELECTRICAL PLAN IS |
| | REQUIRED TO BE DESIGNED AND SIGNED/SEALED BY A DESIGN |
| | PROFESSIONAL. PROVIDE CORRECTION. FS 471.003(2)(H); |
| | 471.025; WPB FBC 107.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |