| 2018-06-29 05:50:08 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. A PORTION OF WORK PROPOSED NOT WITHIN SCOPE OF FIRE |
| | ALARM LICENSE. FS 489.505(7) REQUIRED 120V FEED |
| | NECESSARY TO POWER NEW FACP IS NOT WITHIN SCOPE OF A EF |
| | LICENSE. ELECTRICAL PERMIT REQUIRED FBC 105.1 |
| | |
| | 2. A ZERO INCREASE OF VALUE IS UNACCECTABLE. ORIGINAL |
| | WORK ON THE EXISTING PERMIT HAS BEEN COMPLETED AND |
| | GIVEN A TCO AND DID NOT INCLUDE THE INSTALLTION OF A |
| | NEW FACP. THE INSTALLATION OF A NEW FACP AND THE |
| | ASSOCIATED WORK CANNOT BE DONE WITH A ZERO INCREASE IN |
| | VALUE. PROVIDE CORRECTION OR VALUE WILL BE ADJUSTED BY |
| | CITY OF WPB. FBC 109.3 |
| | |
| | 3. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |