Plan Review Notes
Plan Review Notes For Permit 18060994
Permit Number 18060994
Review Stop E
Sequence Number 1
Notes
Date Text
2018-06-29 05:50:08ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A PORTION OF WORK PROPOSED NOT WITHIN SCOPE OF FIRE
 ALARM LICENSE. FS 489.505(7) REQUIRED 120V FEED
 NECESSARY TO POWER NEW FACP IS NOT WITHIN SCOPE OF A EF
 LICENSE. ELECTRICAL PERMIT REQUIRED FBC 105.1
  
 2. A ZERO INCREASE OF VALUE IS UNACCECTABLE. ORIGINAL
 WORK ON THE EXISTING PERMIT HAS BEEN COMPLETED AND
 GIVEN A TCO AND DID NOT INCLUDE THE INSTALLTION OF A
 NEW FACP. THE INSTALLATION OF A NEW FACP AND THE
 ASSOCIATED WORK CANNOT BE DONE WITH A ZERO INCREASE IN
 VALUE. PROVIDE CORRECTION OR VALUE WILL BE ADJUSTED BY
 CITY OF WPB. FBC 109.3
  
 3. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  