| 2018-06-28 09:12:55 | 1. ENSURE HYDRAULIC CALCULATIONS MATCH AREA INDICATED | | | ON THE PLANS. | | | 2. ENSURE SIDEWALL SPRAY PATTERNS ARE NOT OBSTRUCTED BY | | | CEILING FAN INSTALLATION IN MAIN LIVING AREAS. | | | 3. REVIEW HYDRAULIC CALCULATIONS INFORMATION TO ENSURE | | | ADEQUATE PRESSURE REQUIREMENTS. | | | 4. PROVIDE DATA SHEET FOR TYCO SPRINKLER HEAD 3331 | | | 5. REVIEW UNITS B2-A ON ALL FLOORS AS IT APPEARS TO BE | | | LACKING COVERAGE UNDER SOFFIT. TO BE VERIFIED IN THE | | | FIELD. | | | | | | S. THOMAS | | | 561-8044728 |
|