Plan Review Notes For Permit 18060954
Permit Number 18060954
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-06-22 14:21:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET C 1 - THERE ARE NO INDICATIONS OF REVIEW OR
 COMPLIANCE WITH ANY FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE PROVIDE AND APPLICABLE NOTE.
  
  
  
  
 2) SHEET D 1 - THERE ARE NO INDICATIONS ON THIS SHEET
 THAT THE KITCHEN DOOR IS BEING REMOVED/WALLED OVER AS
 INDICATED ON SHEET S 1.
  
 WILL THIS DOOR REMIAN IN PLACE? HOW IS THIS DOOR BEING
 SECURED?
  
 PLEASE REVISE THE DRAWING ON D 1 TO SHOW INTENT OF THE
 OPENING AND PROVIDE SPECIFIC NOTE DETAILS ON WHAT WILL
 HAPPEN TO THIS OPENING.
  
  
  
 3) SHEET S 1 - IT APPEARS THAT THE PROPOSED PROJECT IS
 REMOVING A DOOR TO THE EXTERIOR IN THE KITCHEN AREA
 LEAVING JUST ONE EXIT DOOR AR MEANS OF ESCAPE WITHIN
 THE DWELLING UNIT.
  
 PER NFPA 101, CHAPTER 31, EXISTING APARTMENT BUILDINGS.
  
 31.2 MEANS OF EGRESS REQUIREMENTS.
 31.2.1 GENERAL.
 31.2.1.1 MEANS OF EGRESS FROM DWELLING UNITS TO THE
 OUTSIDE OF THE
 BUILDING SHALL BE IN ACCORDANCE WITH CHAPTER 7 AND THIS
 CHAPTER.
 31.2.1.2 MEANS OF ESCAPE WITHIN THE DWELLING UNIT SHALL
 COMPLY
 WITH THE PROVISIONS OF SECTION 24.2 FOR ONE- AND
 TWO-FAMILY
 DWELLINGS
  
  
 24.2* MEANS OF ESCAPE REQUIREMENTS.
 24.2.1 GENERAL. THE PROVISIONS OF CHAPTER 7 SHALL NOT
 APPLY TO
 MEANS OF ESCAPE, UNLESS SPECIFICALLY REFERENCED IN THIS
 CHAPTER.
 24.2.2 NUMBER AND TYPES OF MEANS OF ESCAPE.
 24.2.2.1 NUMBER OF MEANS OF ESCAPE.
 24.2.2.1.1 IN DWELLINGS OR DWELLING UNITS OF TWO ROOMS
 OR MORE,
 EVERY SLEEPING ROOM AND EVERY LIVING AREA SHALL HAVE
 NOT LESS THAN
 ONE PRIMARY MEANS OF ESCAPE AND ONE SECONDARY MEANS OF
 ESCAPE.
 24.2.2.1.2 A SECONDARY MEANS OF ESCAPE SHALL NOT BE
 REQUIRED
 WHERE ONE OF THE FOLLOWING CONDITIONS IS MET:
 (1) THE BEDROOM OR LIVING AREA HAS A DOOR LEADING
 DIRECTLY TO THE
 OUTSIDE OF THE BUILDING AT OR TO THE FINISHED GROUND
 LEVEL.
 (2) THE DWELLING UNIT IS PROTECTED THROUGHOUT BY AN
 APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 24.3.5.
 24.2.2.2 PRIMARY MEANS OF ESCAPE. THE PRIMARY MEANS OF
 ESCAPE SHALL BE A DOOR, STAIRWAY, OR RAMP PROVIDING A
 MEANS OF
 UNOBSTRUCTED TRAVEL TO THE OUTSIDE OF THE DWELLING UNIT
 AT STREET OR
 THE FINISHED GROUND LEVEL.
 24.2.2.3 SECONDARY MEANS OF ESCAPE. THE SECONDARY MEANS
 OF
 ESCAPE, OTHER THAN AN EXISTING APPROVED MEANS OF
 ESCAPE, SHALL BE
 ONE OF THE MEANS SPECIFIED IN 24.2.2.3.1 THROUGH
 24.2.2.3.4.
 24.2.2.3.1 IT SHALL BE A DOOR, STAIRWAY, PASSAGE, OR
 HALL PROVIDING A
 WAY OF UNOBSTRUCTED TRAVEL TO THE OUTSIDE OF THE
 DWELLING AT STREET
 OR THE FINISHED GROUND LEVEL THAT IS INDEPENDENT OF AND
 REMOTE
 FROM THE PRIMARY MEANS OF ESCAPE.
 24.2.2.3.2 IT SHALL BE A PASSAGE THROUGH AN ADJACENT
 NONLOCKABLE
 SPACE, INDEPENDENT OF AND REMOTE FROM THE PRIMARY MEANS
 OF
 ESCAPE, TO ANY APPROVED MEANS OF ESCAPE.
 24.2.2.3.3* IT SHALL BE AN OUTSIDE WINDOW OR DOOR
 OPERABLE FROM
 THE INSIDE WITHOUT THE USE OF TOOLS, KEYS, OR SPECIAL
 EFFORT AND SHALL
 PROVIDE A CLEAR OPENING OF NOT LESS THAN 5.7 FT2 (0.53
 M2). THE
 WIDTH SHALL BE NOT LESS THAN 20 IN. (510 MM), AND THE
 HEIGHT SHALL
 BE NOT LESS THAN 24 IN. (610 MM). THE BOTTOM OF THE
 OPENING SHALL
 BE NOT MORE THAN 44 IN. (1120 MM) ABOVE THE FLOOR. SUCH
 MEANS
 OF ESCAPE SHALL BE ACCEPTABLE WHERE ONE OF THE
 FOLLOWING CRITERIA
 IS MET:
 (1) THE WINDOW SHALL BE WITHIN 20 FT (6100 MM) OF THE
 FINISHED
 GROUND LEVEL.
 (2) THE WINDOW SHALL BE DIRECTLY ACCESSIBLE TO FIRE
 DEPARTMENT
 RESCUE APPARATUS AS APPROVED BY THE AUTHORITY HAVING
 JURISDICTION.
 (3) THE WINDOW OR DOOR SHALL OPEN ONTO AN EXTERIOR
 BALCONY.
 (4) WINDOWS HAVING A SILL HEIGHT BELOW THE ADJACENT
 FINISHED
 GROUND LEVEL SHALL BE PROVIDED WITH A WINDOW WELL
 MEETING
 ALL OF THE FOLLOWING CRITERIA:
 (A) THE WINDOW WELL SHALL HAVE HORIZONTAL DIMENSIONS
 THAT
 ALLOW THE WINDOW TO BE FULLY OPENED.
 (B) THE WINDOW WELL SHALL HAVE AN ACCESSIBLE NET CLEAR
 OPENING OF NOT LESS THAN 9 FT2 (0.82 M2) WITH A LENGTH
 AND WIDTH OF NOT LESS THAN 36 IN. (915 MM).
 (C) A WINDOW WELL WITH A VERTICAL DEPTH OF MORE THAN 44
 IN.
 (1120 MM) SHALL BE EQUIPPED WITH AN APPROVED
 PERMANENTLY AFFIXED LADDER OR WITH STEPS MEETING BOTH
 OF THE FOLLOWING CRITERIA:
 I. THE LADDER OR STEPS SHALL NOT ENCROACH MORE THAN 6
 IN. (150 MM) INTO THE REQUIRED DIMENSIONS OF THE
 WINDOW WELL.
 II. THE LADDER OR STEPS SHALL NOT BE OBSTRUCTED BY THE
 WINDOW
  
 THIS BUILDING UNITS WERE DESIGNED TO HAVE TWO EXITS.
  
 PLEASE REVIEW THE ABOVE CODE REFERNCES AND CORRECT OR
 JUSTIFY HAVING ONE EXIT WITH SPECIFIC CODE REFERNECES.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  