| 2018-07-28 07:59:34 | 1) THIS RESUBMITTAL IS A CONVOLUTED MESS AND IN |
| | DISSARAY. THERE ARE TWO DIFFERENT GAS DRWAINGS, |
| | MULTIPLE COPIES OF ONE GAS DRAWING,ONLY ONE COPY OF |
| | ANOTHER, MULTIPLE COPIES OF RINNAI SPECS AND REGULATOR |
| | SPECS. NOTHING IS IN ORDER. THERE ARE MULTIPLE COPIES |
| | OF PERMIT APPLICATIONS, ETC. SOMEONE FROM THE |
| | CONTRACTOR'S OFFICE SHALL COME TO THE BUILDING DIVISION |
| | AND REMOVE ALL THE OLD PLANS AND ARRANGE THESE |
| | DOCUMENTS INTO TWO COMPLETE SETS OF PLANS FOR REVIEW. |
| | WPB AMEND. TO FBC SEC. 107.2.1, 107.1. I WILL NOT DO A |
| | REVIEW UNTIL THIS IS DONE. |
| | 2) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | FOR THE LOW PRESSURE SYSTEM USED TO SIZE THE GAS SYSTEM |
| | OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH |
| | SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD |
| | THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER |
| | TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND |
| | TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. |
| | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. |
| | 3) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| | SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| | 4) ) SUBMIT LEGIBLE COPIES OF THE MANUFACTURER?S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. IDENTIFY ON THE SPECIFICATION SHEETS |
| | WHICH MODEL REGULATOR IS BEING INSTALLED AND THE |
| | ORIFICE SIZE TO ENSURE THE REGULATOR CAN ACCOMMODATE |
| | THE BTU LOAD THROUGH THE REGULATOR.2017 FGC SEC.410.1, |
| | 2017 FBC-RES. SEC. G2421.1. |
| | 5) THE ABANDONED POOL HEATER AND FIREPLACE LINES SHALL |
| | BE EQUIPPED WITH A SHUTOFF VALVE, PRESSURE REGULATOR, A |
| | NIPPLE AND A CAP. 2017 FBC-FUEL GAS SEC.404.15. THIS IS |
| | REQUIRED TO ENSURE THE GAS SYSTEM IS LEFT IN A SAFE |
| | CONDITION. |
| | |