Plan Review Notes
Plan Review Notes For Permit 18060877
Permit Number 18060877
Review Stop G
Sequence Number 2
Notes
Date Text
2018-08-31 06:52:4708/31/2018 2ND GAS REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) A PRIMARY PLUMBING PERMIT IS REQUIRED WITH THE GAS
 PERMIT AS A SUB AND ALSO YOU WILL NEED A ELECTRIC SUB
 PERMIT FOR THIS INSTALLATION. FBC 105.1. 2ND REQUEST.
  
 2) REMOVE ALL PREVIOUS DOCUMENTS THAT ARE NOT
 APPLICABLE AND SUBMIT 2 COMPLETE SETS OF PLANS FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.1.
  
 3) WHAT IS THE PIPING THAT IS BEING USED ABOVE GROUND?
 INDICATE ON THE PLAN. WPB AMEND. TO FBC SEC.
 107.2.1.2ND REQUEST.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. THE
 SUBMITTED DOCUMENTS FOR THE RANGE AND FIREPLACE DO NOT
 SHOW THE APPLIANCES ARE LISTED AND LABELED AND THERE
 ARE NO SPECS ON THE HEATER.
  
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST.
  
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 7) SHOW THE LOCATION OF ALL REGULATORS .SHOW THE
 DISTANCE FROM THE 2 PSI REGULATOR TO THE APPLIANCE.
 COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 OR 2017
 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE PROPER PIPE
 SIZE AND BTU LOAD
  
 8) THERE ARE TWO DIFFERENT SETS OF PARTIAL
 SPECIFICATIONS FOR A TANKLESS WATER HEATER. ONE SET
 APPEARS TO BE BE FOR A TAKAGI BRAND AND ONE SET IS FROM
 RINNAI. WHICH BRAND UNIT IS BEING INSTALLED? CLARIFY ON
 THE PLANS.
  
 9) THE GAS RISER DIAGRAM HAS BEEN ENLARGED AND IS
 DIFFICULT TO READ. THERE ARE PIPE SECTIONS THAT CONNECT
 NOWHERE. SUBMIT A CLEAR GAS PIPING DIGRAM THAT REFLECTS
 THE PIPING INSTALLATION,
  
 VALUATION: THE VALUE OF THIS TANKLESS WATER HEATER
 INSTALL MUST BE OF ACTUAL COST THE SOMEONE WOULD BACK A
 LICENSED CONTRACTOR TO PERFORM THE PLUMBING, GAS, AND
 ELECTRIAL WORK REQUIRED. YOUR VALUE OF $250.00 WOULD
 NOT COVER THE COST OF THE GAS PIPING MATERIAL. PLEASE
 ADJUST YOUR VALUE. WPB AMEND TO THE FBC 109.3
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  