| 2018-08-31 06:52:47 | 08/31/2018 2ND GAS REVIEW**DENIED** |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1) A PRIMARY PLUMBING PERMIT IS REQUIRED WITH THE GAS |
| | PERMIT AS A SUB AND ALSO YOU WILL NEED A ELECTRIC SUB |
| | PERMIT FOR THIS INSTALLATION. FBC 105.1. 2ND REQUEST. |
| | |
| | 2) REMOVE ALL PREVIOUS DOCUMENTS THAT ARE NOT |
| | APPLICABLE AND SUBMIT 2 COMPLETE SETS OF PLANS FOR |
| | REVIEW. WPB AMEND. TO FBC SEC. 107.1. |
| | |
| | 3) WHAT IS THE PIPING THAT IS BEING USED ABOVE GROUND? |
| | INDICATE ON THE PLAN. WPB AMEND. TO FBC SEC. |
| | 107.2.1.2ND REQUEST. |
| | |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. THE |
| | SUBMITTED DOCUMENTS FOR THE RANGE AND FIREPLACE DO NOT |
| | SHOW THE APPLIANCES ARE LISTED AND LABELED AND THERE |
| | ARE NO SPECS ON THE HEATER. |
| | |
| | 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST. |
| | |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| | G2421.1. |
| | |
| | 7) SHOW THE LOCATION OF ALL REGULATORS .SHOW THE |
| | DISTANCE FROM THE 2 PSI REGULATOR TO THE APPLIANCE. |
| | COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 OR 2017 |
| | FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE PROPER PIPE |
| | SIZE AND BTU LOAD |
| | |
| | 8) THERE ARE TWO DIFFERENT SETS OF PARTIAL |
| | SPECIFICATIONS FOR A TANKLESS WATER HEATER. ONE SET |
| | APPEARS TO BE BE FOR A TAKAGI BRAND AND ONE SET IS FROM |
| | RINNAI. WHICH BRAND UNIT IS BEING INSTALLED? CLARIFY ON |
| | THE PLANS. |
| | |
| | 9) THE GAS RISER DIAGRAM HAS BEEN ENLARGED AND IS |
| | DIFFICULT TO READ. THERE ARE PIPE SECTIONS THAT CONNECT |
| | NOWHERE. SUBMIT A CLEAR GAS PIPING DIGRAM THAT REFLECTS |
| | THE PIPING INSTALLATION, |
| | |
| | VALUATION: THE VALUE OF THIS TANKLESS WATER HEATER |
| | INSTALL MUST BE OF ACTUAL COST THE SOMEONE WOULD BACK A |
| | LICENSED CONTRACTOR TO PERFORM THE PLUMBING, GAS, AND |
| | ELECTRIAL WORK REQUIRED. YOUR VALUE OF $250.00 WOULD |
| | NOT COVER THE COST OF THE GAS PIPING MATERIAL. PLEASE |
| | ADJUST YOUR VALUE. WPB AMEND TO THE FBC 109.3 |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |