| Date |
Text |
| 2018-09-12 12:48:49 | CLOUDED REVISION "K" DATED 06/15/18 (REVISION #7) |
| | BUILDING REVIEW COMMENTS. |
| | CODE: FBC 2010 AND CITY AMENDMENTS. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | 1- OK. SEE REVISION #6 SHEET A5.23 |
| | |
| | 2- SHEET A2.0P2: UNABLE TO FIND PARTITION TYPES 11B. |
| | PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THIS |
| | TYPE OF PARTITION. |
| | SEC. 701.1 FBC. |
| | |
| | RESPONSE: |
| | RESPONSE LETTER STATES "ON SHEET A-2.40B, WHICH IS NEW |
| | SHEET ISSUED AFTER REVISION 7. TO BE INCLUDED IN REV |
| | 8". |
| | |
| | SHEET A-2.40B WAS NOT PROVIDED. |
| | THIS IS A LARGE SCALE PROJECT. IT IS VERY DIFFICULT TO |
| | DO A REVIEW IF THE INFORMATION THAT IS LISTED IN THE |
| | SUBMITTED NARRATIVE IS NOT PROVIDED AT TIME OF |
| | SUBMITTAL. THE PLAN REVIEWER HAS NO WAY OF KNOWING IF |
| | THE PROPOSED REVISION WAS SUBMITTED EARLIER OR IF IT'S |
| | PART OF A FUTURE REVISION. PROVIDING A CLEAR AND |
| | CONCISE NARRATIVE FOR THE ACTUAL REVISION ITEMS TO BE |
| | CONSIDERED IN THIS REVISION #7 AND PROVIDING ONLY THE |
| | DRAWINGS THAT ARE REVISED WOULD BE VERY HELPFUL TO |
| | PROVIDE A BETTER SERVICE AND TO AVOID UNNECESSARY |
| | REPETITIVE REVIEWS OF THE SAME ITEMS. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 3- SHEET A2.76A AND A2.76B : PROVIDE COMPLETE |
| | STRUCTURAL FRAMING DETAIL AND SPECIFICATIONS FOR SCREEN |
| | WALL OPENINGS ACCESS. PROVIDE DETAIL FOR REQUIRED |
| | RE-REINFORCEMENT WHEN THE TWO BOTTOM RING BEAMS ARE |
| | REMOVED TO ALLOW FOR THE OPENINGS. SEC. 1609.1 FBC. |
| | |
| | RESPONSE: |
| | RESPONSE LETTER STATES "THIS IS A STEEL STRUCTURE. |
| | THERE IS NO DETAIL BECAUSE THE BEAMS WERE ELIMINATED, |
| | AND SCREEN WALL WAS DELETED IN THIS AREA. NO |
| | RE-REINFORCEMENT REQUIRED." |
| | |
| | THIS ITEM NEEDS TO BE ADDRESSED BY THE DESIGN |
| | PROFESSIONAL OF RECORD FOR THE METAL SCREEN WALL |
| | SYSTEM. THIS WALL SYSTEM IS EXPOSED TO THE WIND LOADS. |
| | FRAMING DETAILS AT NEW OPENINGS ARE REQUIRED. OR |
| | ENGINEER OF RECORD TO PROVIDE ANALYSIS SHOWING WHY IT |
| | IS NOT REQUIRED. SEC. 107.2.1.4 CITY AMENDMENTS. |
| | |
| | 4- SHEET A2.76B: |
| | A)PROVIDE PRODUCT APPROVAL FOR NEW DOUBLE DOOR 2603B AS |
| | REQUIRED BY FAC 61G20-3.001 |
| | |
| | B)DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | RESPONSE LETTER STATES "PRODUCT APPROVALS ARE CURRENTLY |
| | UNDER REVIEW - SEE PERMIT #18030045". |
| | |
| | PRODUCT APPROVAL WAS NOT PROVIDED. NEED PRODUCT |
| | APPROVAL THAT CLEARLY IDENTIFY PROPOSED LOCATION. ALSO, |
| | SUBMITTAL #18030045 IS NOT APPROVED YET AND THERE IS NO |
| | WAY TO IDENTIFY WHICH PRODUCT APPROVAL IS FOR THE DOOR |
| | LISTED IN THIS REVISION. |
| | |
| | 5- OK |
| | |
| | 6- SHEET A5.01: UNABLE TO FIND PARTITION TYPES 11B AND |
| | 53. PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THIS |
| | TYPE OF PARTITIONS. SEC. 701.1 FBC. |
| | |
| | RESPONSE: |
| | SEE MY RESPONSE FOR ITEM #2 ABOVE TO HELP EXPEDITE THE |
| | REVIEW PROCESS. |
| | |
| | 7- SHEET A5.04: UNABLE TO FIND PARTITION TYPES 11B AND |
| | 53. PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THIS |
| | TYPE OF PARTITIONS. SEC. 701.1 FBC. |
| | |
| | RESPONSE: |
| | SEE MY RESPONSE FOR ITEM #2 ABOVE TO HELP EXPEDITE THE |
| | REVIEW PROCESS. |
| | |
| | 8- OK. |
| | |
| | 9- OK. |
| | |
| | 10- SHEET A8.11: UNABLE TO LOCATED REVISED DOOR P240 TO |
| | CHECK IF FIRE RATING IS REQUIRED.. PROVIDE PLANS |
| | SHOWING LOCATION. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | SEE MY RESPONSE FOR ITEM #2 ABOVE TO HELP EXPEDITE THE |
| | REVIEW PROCESS. |
| | |
| | 11- PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |