Plan Review Notes
Plan Review Notes For Permit 18060849
Permit Number 18060849
Review Stop M
Sequence Number 1
Notes
Date Text
2018-07-03 11:14:591ST REVIEW FBC-2010 MECHANICAL
 REVISION #18060849
 MASTER #15111020
 7/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.01: THE REVISON NARRATIVE STATES A/C TO NEW
 AMENITY SERVICE ROOM, HOWEVER I WAS UNABLE TO FIND THE
 NEW SERVICE AMENITY ROOM ON THE MECHANICAL PLAN OR THE
 ARCHITECTURAL PLANS FOR THE LOBBY LEVEL.
  
 2) M2.01: THE REVISED PLAN DOES NOT SHOW THE EMERGENCY
 AND POOL EQUIPMENT ROOMS, AND THE SLAB CEILINGS SHOWN
 ON THE PLAN FOR THE BOH DO NOT MATCH THE GYPSUM
 CEILINGS AS SHOWN ON THE NEW A7.01 REFLECTIVE CEILING
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  