| 2018-07-19 17:44:34 | CLOUDED REVISION "K" DATED 06/15/18 (REVISION #7) |
| | BUILDING REVIEW COMMENTS. |
| | CODE: FBC 2010 AND CITY AMENDMENTS. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | 1- NARRATIVE SUBMITTED STATES THAT THE LOBBY STAIR |
| | WIDTHS WERE REVISED. THERE ARE NO DIMENSIONS GIVEN. |
| | PROVIDE FLOOR PLAN SHOWING THE REVISED DIMENSIONS. SEC. |
| | 1005.1 FBC. |
| | |
| | 2- SHEET A2.0P2: UNABLE TO FIND PARTITION TYPES 11B. |
| | PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THIS |
| | TYPE OF PARTITION. |
| | SEC. 701.1 FBC. |
| | |
| | 3- SHEET A2.76A AND A2.76B : PROVIDE COMPLETE |
| | STRUCTURAL FRAMING DETAIL AND SPECIFICATIONS FOR SCREEN |
| | WALL OPENINGS ACCESS. PROVIDE DETAIL FOR REQUIRED |
| | RE-REINFORCEMENT WHEN THE TWO BOTTOM RING BEAMS ARE |
| | REMOVED TO ALLOW FOR THE OPENINGS. SEC. 1609.1 FBC. |
| | |
| | 4- SHEET A2.76B: |
| | A)PROVIDE PRODUCT APPROVAL FOR NEW DOUBLE DOOR 2603B AS |
| | REQUIRED BY FAC 61G20-3.001 |
| | |
| | B)DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 5- IT IS NOT CLEAR HOW MANY DRAWINGS WERE REVISED. |
| | THERE ARE MANY SHEETS THAT ARE LISTED IN THE NARRATIVE |
| | SUBMITTED BUT I WAS UNABLE TO FIND THEM IN THE DRAWINGS |
| | SUBMITTED. PLEASE CORRELATE NARRATIVE #7 WITH DRAWINGS |
| | SUBMITTED TO AVOID CONFLICTS/DELAYS. SEC. 107.2.1 CITY |
| | AMENDMENTS. FOR EXAMPLE WERE ARE DRAWINGS: A2.53A, |
| | A2.56A, A2.66A, A2.68A, A2.70A, A2.71A, A2.72A, A2.73A, |
| | A2.75A, A2.56B, A2.66B, A2.68B, A2.69A, A2.70B, A2.71B, |
| | A2.72B, A2.73B, A2.75B, A4.11, A4.12, A5.02, A5.03, |
| | A5.04, A5.05, A5.06, A5.15, A5.23, A6.64, A7.16, |
| | A7.66B. |
| | |
| | 6- SHEET A5.01: UNABLE TO FIND PARTITION TYPES 11B AND |
| | 53. PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THIS |
| | TYPE OF PARTITIONS. SEC. 701.1 FBC. |
| | |
| | 7- SHEET A5.04: UNABLE TO FIND PARTITION TYPES 11B AND |
| | 53. PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THIS |
| | TYPE OF PARTITIONS. SEC. 701.1 FBC. |
| | |
| | 8- SHEET A6-88: |
| | A)STAIR HANDRAIL DETAILS 8 AND 9 DON'T COMPLY WITH THE |
| | HANDRAIL GRIPPING SURFACE OF SEC. 1012.3 FBC AND SEC. |
| | 505.7.2 FBC-ACCESSIBILITY. REVISE AS REQUIRED. |
| | |
| | B) IT LOOKS LIKE STAIR TREAD SECTION DETAIL #6 SHOWS |
| | OPEN RISERS. OPEN RISER ARE NOT ALLOWED. SEC. 1009.4.5 |
| | FBC AND SEC. 504.3 FBC ACCESSIBILITY DOESN'T ALLOW OPEN |
| | RISERS. REVISE AS REQUIRED. |
| | |
| | C) PROVIDE STAIR NOSING INFORMATION SHOWING COMPLIANCE |
| | WITH SEC. 1009.4.5 FBC AND 504.5 FBC- ACCESSIBILITY. |
| | |
| | 9- SHEET A7-10: THERE IS A REVISION "K" WITH A NOTE |
| | STATING TO SEE SHEET A7.90-16A. WHERE IS SHEET |
| | A7.90-16A?. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 10- SHEET A8.11: UNABLE TO LOCATED REVISED DOOR P240 TO |
| | CHECK IF FIRE RATING IS REQUIRED.. PROVIDE PLANS |
| | SHOWING LOCATION. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 11- PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |