2018-07-19 17:44:34CLOUDED REVISION "K" DATED 06/15/18 (REVISION #7)
 BUILDING REVIEW COMMENTS.
 CODE: FBC 2010 AND CITY AMENDMENTS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
 1- NARRATIVE SUBMITTED STATES THAT THE LOBBY STAIR
 WIDTHS WERE REVISED. THERE ARE NO DIMENSIONS GIVEN.
 PROVIDE FLOOR PLAN SHOWING THE REVISED DIMENSIONS. SEC.
 1005.1 FBC.
  
 2- SHEET A2.0P2: UNABLE TO FIND PARTITION TYPES 11B.
 PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THIS
 TYPE OF PARTITION.
 SEC. 701.1 FBC.
  
 3- SHEET A2.76A AND A2.76B : PROVIDE COMPLETE
 STRUCTURAL FRAMING DETAIL AND SPECIFICATIONS FOR SCREEN
 WALL OPENINGS ACCESS. PROVIDE DETAIL FOR REQUIRED
 RE-REINFORCEMENT WHEN THE TWO BOTTOM RING BEAMS ARE
 REMOVED TO ALLOW FOR THE OPENINGS. SEC. 1609.1 FBC.
  
 4- SHEET A2.76B:
 A)PROVIDE PRODUCT APPROVAL FOR NEW DOUBLE DOOR 2603B AS
 REQUIRED BY FAC 61G20-3.001
  
 B)DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- IT IS NOT CLEAR HOW MANY DRAWINGS WERE REVISED.
 THERE ARE MANY SHEETS THAT ARE LISTED IN THE NARRATIVE
 SUBMITTED BUT I WAS UNABLE TO FIND THEM IN THE DRAWINGS
 SUBMITTED. PLEASE CORRELATE NARRATIVE #7 WITH DRAWINGS
 SUBMITTED TO AVOID CONFLICTS/DELAYS. SEC. 107.2.1 CITY
 AMENDMENTS. FOR EXAMPLE WERE ARE DRAWINGS: A2.53A,
 A2.56A, A2.66A, A2.68A, A2.70A, A2.71A, A2.72A, A2.73A,
 A2.75A, A2.56B, A2.66B, A2.68B, A2.69A, A2.70B, A2.71B,
 A2.72B, A2.73B, A2.75B, A4.11, A4.12, A5.02, A5.03,
 A5.04, A5.05, A5.06, A5.15, A5.23, A6.64, A7.16,
 A7.66B.
  
 6- SHEET A5.01: UNABLE TO FIND PARTITION TYPES 11B AND
 53. PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THIS
 TYPE OF PARTITIONS. SEC. 701.1 FBC.
  
 7- SHEET A5.04: UNABLE TO FIND PARTITION TYPES 11B AND
 53. PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THIS
 TYPE OF PARTITIONS. SEC. 701.1 FBC.
  
 8- SHEET A6-88:
 A)STAIR HANDRAIL DETAILS 8 AND 9 DON'T COMPLY WITH THE
 HANDRAIL GRIPPING SURFACE OF SEC. 1012.3 FBC AND SEC.
 505.7.2 FBC-ACCESSIBILITY. REVISE AS REQUIRED.
  
 B) IT LOOKS LIKE STAIR TREAD SECTION DETAIL #6 SHOWS
 OPEN RISERS. OPEN RISER ARE NOT ALLOWED. SEC. 1009.4.5
 FBC AND SEC. 504.3 FBC ACCESSIBILITY DOESN'T ALLOW OPEN
 RISERS. REVISE AS REQUIRED.
  
 C) PROVIDE STAIR NOSING INFORMATION SHOWING COMPLIANCE
 WITH SEC. 1009.4.5 FBC AND 504.5 FBC- ACCESSIBILITY.
  
 9- SHEET A7-10: THERE IS A REVISION "K" WITH A NOTE
 STATING TO SEE SHEET A7.90-16A. WHERE IS SHEET
 A7.90-16A?.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 10- SHEET A8.11: UNABLE TO LOCATED REVISED DOOR P240 TO
 CHECK IF FIRE RATING IS REQUIRED.. PROVIDE PLANS
 SHOWING LOCATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 11- PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  