| 2018-06-30 08:49:13 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | EXISTING SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD |
| | SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| | ANY SUB-PANEL(S) NEC 215.5; WPB FBC 107.2.1 |
| | |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS. |
| | NEC 210.8, 210.12, 215.5, 408.4; WPB FBC 107.3.5; FBC |
| | RE E3706.2, E3902 |
| | |
| | 3. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON |
| | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS |
| | 481.229; WPB FBC 107.2.1, 107.3.5.1.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |