2018-06-29 17:17:421ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
  
 1. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL. THE
 REAR WALL GRAB BAR SHALLL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 2. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER
  
 3. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC
 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4. SHT. P101 THE FIRE STOPPING DETAILS ARE ILLEGIBLE
 PLEASE CLARIFY . PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. P101 THE VENT ON THE WATER CLOSET IS A CODE
 VIOLATION A DRY VENT CANNOT RUN HORIZONTAL UNTIL IT IS
 A MIN OF 6" ABOVE FLOOD LEVEL RIM OF THE FIXTURE. IF
 YOU CONNECT THE LAVATORY BRANCH DRAIN TO THE TOILET
 BRANCH DRAIN IT WILL BE A WET VENT A COMPLY WITH THE
 CODE . PER FBC PL 912.1
  
 6. THE LAVATORY IN THE ACCESSIBLE BATHROOM SHAL HAVE
 TEMPERED WATER DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  