| Plan Review Notes For Permit 18060764 |
| Permit Number |
18060764 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-21 15:30:24 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE NO INDICATIONS OF HOW THE MECHANICAL | | | VENTILATION/MAKE UP AIR FOR THE SMOKE CONTROL SYSTEM | | | WILL BE MAINTAINED AND CONTROLLED THROUGHOUT THIS | | | CONSTRUCTION PROJECT. | | | | | | THERE ARE LARGE INTAKE OPENINGS AT THIS EXISTING SLAB | | | SITE THAT ARE NOT CLEARLY IIDENTIFIED ON THE PLAN | | | SHEETS. | | | | | | PLEASE PROVIDE DETAILS ON HOW THIS SYSTEM WILL BE | | | MAINTAINED AND/OR BUILT OUT. | | | | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|