| 2018-06-29 15:53:10 | 06/29/2018 1ST GAS REVIEW**DENIED** |
| | |
| | 1) YOUR PLANS ARE REFERENCING THE 2007 AND 2014 FBC. |
| | THE CODE IN AFFECT AT THIS TIME IS THE 2017 6TH ED OF |
| | THE FBC. YOU HAVE NOT INCLUDED A 2 PSI IZING CHART |
| | EITHER. SUBMIT TWO COPIES OF THE APPLICABLE SIZING |
| | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON |
| | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) |
| | FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN |
| | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 |
| | FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES |
| | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. |
| | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. |
| | |
| | 2) PLAN IS SHOWING SYSTEM AS 2 PSI BUT YOUR PLAN DOES |
| | NOT SHOW NOR HAVE YOU INCLUDED THE MANUFACTURES |
| | INSTALLATION MANUALS FOR THE PRESSURE REGULATORS. |
| | SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE |
| | REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| | BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION. |
| | 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421. |
| | |
| | 3) TOTAL JOB VALUE SEEM LOW. PROVIDE A SIGNED BONA FIDE |
| | CONTRACT SHOWING THE COMPLETE COST OF THE GENERATOR |
| | INSTALLED. FBC 109.3 |
| | |
| | 4) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| | SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| | |
| | 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 |
| | OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE |
| | PROPER PIPE SIZE AND BTU LOAD. |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |