Plan Review Notes
Plan Review Notes For Permit 18060719
Permit Number 18060719
Review Stop G
Sequence Number 1
Notes
Date Text
2018-06-29 15:53:1006/29/2018 1ST GAS REVIEW**DENIED**
  
 1) YOUR PLANS ARE REFERENCING THE 2007 AND 2014 FBC.
 THE CODE IN AFFECT AT THIS TIME IS THE 2017 6TH ED OF
 THE FBC. YOU HAVE NOT INCLUDED A 2 PSI IZING CHART
 EITHER. SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
  
 2) PLAN IS SHOWING SYSTEM AS 2 PSI BUT YOUR PLAN DOES
 NOT SHOW NOR HAVE YOU INCLUDED THE MANUFACTURES
 INSTALLATION MANUALS FOR THE PRESSURE REGULATORS.
 SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION.
 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.
  
 3) TOTAL JOB VALUE SEEM LOW. PROVIDE A SIGNED BONA FIDE
 CONTRACT SHOWING THE COMPLETE COST OF THE GENERATOR
 INSTALLED. FBC 109.3
  
 4) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]