2018-07-10 17:38:051ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE NEW SIDE GRAB BAR SHALL COMPLY WITH FBC ACC
 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL.
  
 2. THE BRANCH DRAIN FOR THE BREAKROOM SINK SHALL
 CONNECT TO THE BUILDING DRAIN DOWN STREAM OF THE
 EXISTING BATHROOM GROUP. PER FBC PL 912.1
  
 3. HOT WATER IS REQUIRED FOR THE BREAKROOM SINK. PER
 FBC PL 607.1
  
 4. PLEASE PROVIDE A COST BREAKDOWN TO SHOW COMPLIANCE
 WITH FBC ACC 202.4, 202.4.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  