| Plan Review Notes For Permit 18060693 |
| Permit Number |
18060693 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-10 17:38:05 | 1ST REVIEW: FBC 2017 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE NEW SIDE GRAB BAR SHALL COMPLY WITH FBC ACC | | | 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42 | | | INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE | | | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR | | | WALL. | | | | | | 2. THE BRANCH DRAIN FOR THE BREAKROOM SINK SHALL | | | CONNECT TO THE BUILDING DRAIN DOWN STREAM OF THE | | | EXISTING BATHROOM GROUP. PER FBC PL 912.1 | | | | | | 3. HOT WATER IS REQUIRED FOR THE BREAKROOM SINK. PER | | | FBC PL 607.1 | | | | | | 4. PLEASE PROVIDE A COST BREAKDOWN TO SHOW COMPLIANCE | | | WITH FBC ACC 202.4, 202.4.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | |
|