Plan Review Notes
Plan Review Notes For Permit 18060684
Permit Number 18060684
Review Stop P
Sequence Number 2
Notes
Date Text
2018-11-29 13:57:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 PLUMBING COMMENTS: DENIED
  
 1. RESPONCE TO ITEM #2 OF THE 1ST REVIEW IS STILL
 INCORRECT. DRY VENTS MUST RISE VERTICALLY FROM THE
 DRAIN BEING VENTED PER FBC RES P3104.3 AND
 P3404.4.PROVIDE A CORRECTED PLUMBING ISOMETRIC REMOVING
 THE FLAT DRYVENTS AND ONLY SHOWING WET VENTING AS
 REQUIRED FBC RES P3108.1
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  