Plan Review Notes
Plan Review Notes For Permit 18060684
Permit Number 18060684
Review Stop P
Sequence Number 1
Notes
Date Text
2018-07-30 10:13:4107/30/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) VALUE.THE VALUE SEEM'S TOO LOW AND MUST BE ACTUAL
 VALUE.109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED
  
 2) PROVIDE A CORRECTED PLUMBING ISOMETRIC REMOVING THE
 FLAT DRYVENTS AND ONLY SHOWING WET VENTING AS REQUIRED
 FBC R P3108.1
  
 3) SHT. A-1 CALLS OUT FOR A TANKLESS WATER HEATER (HWH)
 BUT YOUR FORM R405-2017 IS CALLING OUT A 40 GALLON TANK
 HWH WITH A E.F OF .97. PLEASE CLARIFY WHICH HEATER IS
 BEING USED AND PROVIDE THE FULL INSTALLATION MANUAL.
 PLEASE BE ADVISED I HAVE NEVER COME ACROSS AN ELC
 TANKLESS WITH THAT HIGH VALUE E.F RATING AND THIS MAY
 AFFECT THE OVERALL R405-2017 FORM.
  
 4) TANKLESS MUST BE ABLE TO SUPPLY ALL HOT WATER
 FIXTURE ALL FULL DEMAND. FBC R P2903.1
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  