| 2018-07-10 14:53:50 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN |
| | EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE |
| | CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 |
| | 2. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A |
| | SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL |
| | GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN |
| | ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE |
| | EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. |
| | NEC 250.53(A)(2); FBC RE E3608.4 |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 4. AFCI PROTECTION NOTED ON PLAN IS NOT CODE COMPLIANT. |
| | PER CODE, ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| | CORRECTION. NEC 210.12; FBC RE E3902.16 |
| | 5. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| | OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER. |
| | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 |
| | 6. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | 7. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE E4002.14 |
| | 8. LIGHT IN MASTER CLOSET APPEARS TO BE STANDARD RECESS |
| | LIGHTS. PER CODE: LIGHTING WITH OPEN OR PARTIALLY |
| | ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS |
| | SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE |
| | CORRECTION. NEC 410.16; FBC RE E4003.12 |
| | 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| | NEC 110.3, 110.9 |
| | 10. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |