2018-07-12 17:53:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC RESIDENTIAL SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF A DRAINAGE PLAN THAT COMPLIES
 WITH FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS
 SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING. FBC 107.2.5 THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY. IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL
 SHOW CONSTRUCTION TO BE DEMOLISHED AND THE LOCATION AND
 SIZE OF EXISTING STRUCTURES AND CONSTRUCTION THAT ARE
 TO REMAIN ON THE SITE OR PLOT.
  
 2) THE WOOD FRAME STUCCO WALLS ARE REQUIRED TO COMPLY
 WITH FBC-R703.7 EXTERIOR PLASTER. INSTALLATION OF THESE
 MATERIALS SHALL BE IN COMPLIANCE WITH ASTM C926, ASTM
 C1063 AND THE PROVISIONS OF THIS CODE.
  
 2A) FBC-R703.7.2.1 WEEP SCREEDS. A MINIMUM 0.019-INCH
 (0.5 MM) (NO. 26 GALVANIZED SHEET GAGE),
 CORROSION-RESISTANT WEEP SCREED OR PLASTIC WEEP SCREED,
 WITH A MINIMUM VERTICAL ATTACHMENT FLANGE OF 31/2
 INCHES (89 MM) SHALL BE PROVIDED AT OR BELOW THE
 FOUNDATION PLATE LINE ON EXTERIOR STUD WALLS IN
 ACCORDANCE WITH ASTM C926. THE WEEP SCREED SHALL BE
 PLACED NOT LESS THAN 4 INCHES (102 MM) ABOVE THE EARTH
 OR 2 INCHES (51 MM) ABOVE PAVED AREAS AND SHALL BE OF A
 TYPE THAT WILL ALLOW TRAPPED WATER TO DRAIN TO THE
 EXTERIOR OF THE BUILDING. THE WEATHER-RESISTANT BARRIER
 SHALL LAP THE ATTACHMENT FLANGE. THE EXTERIOR LATH
 SHALL COVER AND TERMINATE ON THE ATTACHMENT FLANGE OF
 THE WEEP SCREED.
  
 2B) FBC-R703.7.3 WATER-RESISTIVE BARRIERS.
 WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED
 IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED
 SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION
 R703.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS.
  
 3C) TABLE FBC-R702.1(1) REQUIRES EXTERIOR CEMENT
 PLASTER ON WIRE LATH TO HAVE A MINIMUM THICKNESS OF 7/8
 INCH.
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES.
 4A) THE PRODUCT APPROVALS HAVE NOT BEEN APPROVED AND
 ACCEPTED IN WRITING BY THE DOR.
 4B) THE FLORIDA PRODUCT APPROVAL DRAWINGS THAT WERE
 SUBMITTED ARE REQUIRED TO HAVE THE COVERSHEETS WITH THE
 FL NUMBERS THAT LIST THE DRAWING NUMBERS.
 4C) THE PRODUCT APPROVALS FOR THE IMPACT RATED GLASS
 BLOCK, FIXED WINDOWS, STRUCTURAL MULLIONS AND
 HORIZONTAL ROLLING WINDOWS WERE NOT SUBMITTED.
 4D) THE SPECIFIC ITEMS THAT YOU ARE PROPOSING TO BE
 INSTALLED AND THEIR DESIGN PRESSURES NEED TO BE MARKED
 ON THE PRODUCT APPROVAL SUBMITTALS. THERE ARE SEVERAL
 DIFFERENT TYPES OF THE ITEMS LISTED IN THE PRODUCT
 APPROVALS.
  
 5) THE PRODUCT APPROVAL FOR THE SINGLE HUNG WINDOW (NOA
 NO. 15-0602.06) IS SUPERSEDED BY NOA NO. 18-0124.06.
 SUBMIT THE CURRENT ONE.
  
 6) THE PLANS SPECIFY AN OVERHEAD GARAGE DOOR THAT IS 8'
 IN HEIGHT AND THE PRODUCT APPROVALS ARE FOR AN 8' HIGH
 DOOR. IN THE SUBMITTAL DOCUMENTS, THERE IS WHAT APPEARS
 TO BE A HOME DEPOT ORDER FORM FOR A 7' HIGH GARAGE
 OVERHEAD DOOR. PLEASE CLARIFY.
  
 7) THERE ARE PRODUCT APPROVALS FOR TWO DIFFERENT GARAGE
 DOORS HAVING DIFFERENT DESIGN PRESSURES WITH THE
 SUBMITTAL DOCUMENTS. MARK AS VOID OR REMOVE FROM THE
 PERMIT DOCUMENTS THE ONE THAT WILL NOT BE USED.
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  