| 2018-07-03 14:48:07 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18060681 |
| | 7/3/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PROPOSED PROJECT IS CLASSIFIED AS A CHANGE OF |
| | OCCUPANCY PER SECTION 202 FBC EX, AND THEREFORE SHALL |
| | BE IN COMPLIANCE WITH SECTIONS C503.2 AND C505.1 FBC |
| | EC. THE SUBMITTED ENERGY FORM C402-2017 IS VALID FOR |
| | ALTERATIONS, RENOVATIONS, AND BUILDING SYSTEMS. IN |
| | ACCORDANCE WITH SECTION C101.5.1 APPROVED SOFTWARE SUCH |
| | AS ENERGYGAUGE OR COMCHECK SHALL BE USED TO SHOW |
| | COMPLIANCE. |
| | |
| | 2) SHEET M1: EXHAUST AT A RATE OF .75 CFM PER SQ. FT. |
| | IS REQUIRED FOR THE KITCHEN, AND RECIRCULATION OF AIR |
| | FROM THE KITCHEN IS PROHIBITED- PLEASE REMOVE THE |
| | RETURN DUCTS AND GRILLS FROM THE KITCHEN AND ADJOINING |
| | STORAGE/LAUNDRY ROOM. |
| | |
| | 3) SHEET M1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE OVENS AND ANY OTHER COOKING APPLIANCES IN THE |
| | KITCHEN. REFER TO SECTIONS 507.2 AND 507.3 FBC M AND |
| | PROVIDE EITHER A TYPE I OR TYPE II EXHAUST HOOD. PLEASE |
| | NOTE THE MAIN PLANS SHALL SHOW THE HOOD AND |
| | SPECIFICATIONS BUT THE INSTALLATION SHALL BE DONE UNDER |
| | SEPARATE PERMIT- SECTION 107.2.1.3 WPB. |
| | |
| | 4) PROVIDE AIR BALANCE CALCULATIONS- SECTION 508.1 FBC |
| | M. |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER |
| | PER SECTION 504.1 FBC M, AND INDICATE HOW MAKEUP AIR IS |
| | BEING PROVIDED- SECTION 504.6 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |