| 2018-06-15 16:28:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE IS AN INDICATION OF A WATER SUPPLY LINE. | | | | | | IS THIS SUPPLY LINE A DEDICATED FIRE MAIN OR DOMESTIC? | | | | | | PLEASE REVIEW AND PROVIDE DETAIL COMMENTS. | | | | | | | | | | | | 2) THERE ARE NO HYDRALIC CALCULATIONS SUBMITTED. | | | | | | PLEASE PROVIDE THE PROPER CALUCLATIONS FOR THIS | | | INSTALLATION THAT MEET THE REQUIREMENTS OF THE INTENDED | | | DESIGN. | | | | | | | | | | | | 3) THERE IS AN INDICATION OF AN INCORRECT EDITION OF | | | NFPA 13. | | | | | | THE CURRENT EDITION IS 2013. | | | | | | PLEASE ENSURE THE INSTALLATION MEETS THE REQUIREMENTS | | | OF THE CURRENT EDITION AND CORRECT THE NOTE. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|