Plan Review Notes
Plan Review Notes For Permit 18060660
Permit Number 18060660
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-06-15 16:28:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS AN INDICATION OF A WATER SUPPLY LINE.
  
 IS THIS SUPPLY LINE A DEDICATED FIRE MAIN OR DOMESTIC?
  
 PLEASE REVIEW AND PROVIDE DETAIL COMMENTS.
  
  
  
 2) THERE ARE NO HYDRALIC CALCULATIONS SUBMITTED.
  
 PLEASE PROVIDE THE PROPER CALUCLATIONS FOR THIS
 INSTALLATION THAT MEET THE REQUIREMENTS OF THE INTENDED
 DESIGN.
  
  
  
 3) THERE IS AN INDICATION OF AN INCORRECT EDITION OF
 NFPA 13.
  
 THE CURRENT EDITION IS 2013.
  
 PLEASE ENSURE THE INSTALLATION MEETS THE REQUIREMENTS
 OF THE CURRENT EDITION AND CORRECT THE NOTE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  