Plan Review Notes
Plan Review Notes For Permit 18060652
Permit Number 18060652
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-21 17:01:12BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE FOLLOWING NEEDS TO BE CORRECTED FOR THE STORM
 PANELS, FL11964-R4.
 1A. SHUTTER SCHEDULE SPECIFIES DM - DIRECT MOUNT.
 DETAILS CIRCLED ON PA ARE FOR STUDDED ANGLES.
 1B. SHUTTER GLASS SEPERATION ON SHUTTER SCHEDULE
 SPECIFIES N/A. REQUIREMENTS FOR GLASS SEPERATION ON PA
 IS MINIMUM 1 INCH.
 1C. MINIMUM EDGE DISTANCE FOR FASTENERS ON SHUTTER
 SCHEDULE SPECIFIES 1 1/2 INCH. MINIMUM EDGE DISTANCE ON
 PA IS 3 INJCHES FOR DIRECT MOUNT SOLID SET SYSTEM.
 1D. SUBSTRATE SPECIFIED ON SHUTTER SCHEDULE IS
 CONCRETE. BUILDING WAS BUILT IN 1950. PROVIDE
 DOCUMENTATION WALL IS SOLID CONCRETE NOT CMU.
  
 2. THE FOLLWING NEEDS TO BE CORRECTED FOR THE ACCORDIAN
 SHUTTERS, FL1850-R14.
 2A. EXPLAIN WHAT SHUTTER MOUNTING TYPE A/D IS.
 2B. ON PAGE 11 OF 20 OF THE PA SELECT SCHEDULE TO BE
 USED. THREE SEPERATE SCHEDULES HAVE BEEN SELECTED.
 2C. SEPERATION TO GLASS FOR OPPOSING CENTERMATES IS 4
 INCHES.
  
 CONTRACTOR MAY REQUEST AN IN-PERSON REVIEW PRIOR TO
 RESUBMITTAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  