Plan Review Notes
Plan Review Notes For Permit 18060620
Permit Number 18060620
Review Stop P
Sequence Number 1
Notes
Date Text
2018-07-11 14:47:541ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-2 THE SANITARY ISOMETRIC HAS MULTIPLE CODE
 VIOLATIONS PLEASE CORRECT THE FOLLOWING
 A) THE TOILET IN BATHROOM 1 IS NOT VENTED IT SHOULD BE
 VENTED BY THE LAVATORY VENT STACK THE LAVATORY AND THE
 SHOWER SHOULD CONNECT TO THE TOILET BRANCH DRAIN FOR A
 WET VENTED BATHROOM GROUP
 B) THE LAVATORY IN BATHROOM 1 SHALL HAVE A VENT THROUGH
 THE ROOF OR AN AAV.
 C) THE BBQ KITCHEN SINK SHALL CONNECT SEPARATELY TO THE
 BUILDING DRAIN IT CANNOT CONNECT TO THE BATHROOM GROUP.
 D) THE POWDER ROOM LAVATORY AND TOILET ARE NOT VENTED
 THE LAVATORY SHALL CONNECT TO THE TOILET BRANCH DRAIN
 BEFORE CONNECTING TO THE BUILDING DRAIN THE LAVATORY
 VENT SHALL GO THROUGH THE ROOF OR HAVE A AAV.
 E) THE DRY VENT UPSTREAM OF THE MASTER BATH TOILET IS A
 CODE VIOLATION A DRY VENT CANNOT RUN HORIZONTALLY
 BEFORE IT RUNS VERTICALLY ABOVE THE FLOOD LEVEL RIM OF
 THE FIXTURE THIS VENT IS NOT REQUIRED THE TOILET IS
 VENTED BY THE LAVATORY.
 F) IN THE MASTER BATHROOM THE TUB SHALL CONNECT DOWN
 STREAM OF THE LAVATORY YOU CANNOT HAVE 2 FIXTURES
 UPSTREAM OF THE WET VENT CONNECTION.
 G) IN BATHROOM 2 THE TOILET AND THE TUB SHOULD CONNECT
 TO THE BRANCH FOR THE LAVATORY TO CREATE A WET VENTED
 BATHROOM GROUP AND CONNECT TO THE BUILDING DRAIN
 SEPARATELY FROM THE SOIL STACK FROM 2ND FLOOR AND
 LAUNDRY SINK.
 PER FBC PL P3101.2.1, P3108.1,
  
 2. THE ENERGY CALCULATION LIST A 40 GAL ELECTRIC WATER
 HEATER THE PLAN SHOWS 2 GAS TANKLESS PLEASE CLARIFY.
 PER AMEND TO FBC 107.2.1
  
 3. PLEASE REVISE THE FLOOR PLAN TO REFLECT A REVISED
 SANITARY ISOMETRIC. PER AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  