| 2018-07-11 14:47:54 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. P-2 THE SANITARY ISOMETRIC HAS MULTIPLE CODE |
| | VIOLATIONS PLEASE CORRECT THE FOLLOWING |
| | A) THE TOILET IN BATHROOM 1 IS NOT VENTED IT SHOULD BE |
| | VENTED BY THE LAVATORY VENT STACK THE LAVATORY AND THE |
| | SHOWER SHOULD CONNECT TO THE TOILET BRANCH DRAIN FOR A |
| | WET VENTED BATHROOM GROUP |
| | B) THE LAVATORY IN BATHROOM 1 SHALL HAVE A VENT THROUGH |
| | THE ROOF OR AN AAV. |
| | C) THE BBQ KITCHEN SINK SHALL CONNECT SEPARATELY TO THE |
| | BUILDING DRAIN IT CANNOT CONNECT TO THE BATHROOM GROUP. |
| | D) THE POWDER ROOM LAVATORY AND TOILET ARE NOT VENTED |
| | THE LAVATORY SHALL CONNECT TO THE TOILET BRANCH DRAIN |
| | BEFORE CONNECTING TO THE BUILDING DRAIN THE LAVATORY |
| | VENT SHALL GO THROUGH THE ROOF OR HAVE A AAV. |
| | E) THE DRY VENT UPSTREAM OF THE MASTER BATH TOILET IS A |
| | CODE VIOLATION A DRY VENT CANNOT RUN HORIZONTALLY |
| | BEFORE IT RUNS VERTICALLY ABOVE THE FLOOD LEVEL RIM OF |
| | THE FIXTURE THIS VENT IS NOT REQUIRED THE TOILET IS |
| | VENTED BY THE LAVATORY. |
| | F) IN THE MASTER BATHROOM THE TUB SHALL CONNECT DOWN |
| | STREAM OF THE LAVATORY YOU CANNOT HAVE 2 FIXTURES |
| | UPSTREAM OF THE WET VENT CONNECTION. |
| | G) IN BATHROOM 2 THE TOILET AND THE TUB SHOULD CONNECT |
| | TO THE BRANCH FOR THE LAVATORY TO CREATE A WET VENTED |
| | BATHROOM GROUP AND CONNECT TO THE BUILDING DRAIN |
| | SEPARATELY FROM THE SOIL STACK FROM 2ND FLOOR AND |
| | LAUNDRY SINK. |
| | PER FBC PL P3101.2.1, P3108.1, |
| | |
| | 2. THE ENERGY CALCULATION LIST A 40 GAL ELECTRIC WATER |
| | HEATER THE PLAN SHOWS 2 GAS TANKLESS PLEASE CLARIFY. |
| | PER AMEND TO FBC 107.2.1 |
| | |
| | 3. PLEASE REVISE THE FLOOR PLAN TO REFLECT A REVISED |
| | SANITARY ISOMETRIC. PER AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |