2018-07-16 16:56:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-3 STATES THAT ALL ELECTRICAL SHALL COMPLY
 WITH NEC 2014, BUT THEN IN SEVERAL LOCATIONS AFTER THAT
 THE 2008 OR 2011 NEC IS STATED AS BASIS FOR DESIGN.
 CORRECT ALL DISCREPANCIES ON PLAN. WPB FBC 107.2.1
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 3. AIC RATING OF PANELS IN PANEL SCHEDULES CONFLICTS
 WITH WHAT IS STATED IN THE RISER DIAGRAM. CORRECT ALL
 DISCREPANCIES ON PLAN. WPB FBC 107.2.1
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 5. PROVIDE ACCURATE LOAD CALCULATION. PANEL P IS NOT
 PERMITTED TO USE DEMAND FACTORS AS IT IS A 60 AMP
 PANEL. PANEL B IS NOT PERMITTED TO USE DEMAND FACTORS
 AS IT IS A 60 AMP PANEL. PANEL A SHOWS VALUES FOR
 AC/AHU THAT CONFLICT WITH WHAT IS LISTED IN CIRCUIT
 DESCRIPTION. NEC 215.2, 220.82, 408.30; FBC RE E3602.2
 6. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE
 OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING
 UNIT. NEC 210.52(E)(3); FBC RE E3901.7
 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE E3901.2.1
 8. BE ADVISED THAT GENERATORS AND SWIMMING POOLS ARE
 NOT INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE
 A BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS
 AND PLAN SUBMITTALS FOR THESE SYSTEMS. WPB FBC 105.1,
 107.2.1
 9. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 680.21(C); FBC RE E4203.1.3
 10. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 11. ALL 120 VOLT RECEPTACLE OUTLETS INSTALLED IN
 LAUNDRY AREAS SHALL HAVE GFCI AND AFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8(A)(9), 210.12(A); FBC RE
 E3902.9, 3902.16
 12. PANEL P APPEARS TO NOT HAVE THE CLEARANCE REQUIRED
 PER CODE. PROVIDE CORRECTION. NEC 110.26; FBC RE
 E3405.1
 13. PLAN DOES NOT SHOW THE LOCATION OF ATS SHOWN ON
 RISER DIAGRAM. PROVIDE CORRECTION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER