| 2018-07-16 16:56:43 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHEET E-3 STATES THAT ALL ELECTRICAL SHALL COMPLY |
| | WITH NEC 2014, BUT THEN IN SEVERAL LOCATIONS AFTER THAT |
| | THE 2008 OR 2011 NEC IS STATED AS BASIS FOR DESIGN. |
| | CORRECT ALL DISCREPANCIES ON PLAN. WPB FBC 107.2.1 |
| | 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 3. AIC RATING OF PANELS IN PANEL SCHEDULES CONFLICTS |
| | WITH WHAT IS STATED IN THE RISER DIAGRAM. CORRECT ALL |
| | DISCREPANCIES ON PLAN. WPB FBC 107.2.1 |
| | 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 5. PROVIDE ACCURATE LOAD CALCULATION. PANEL P IS NOT |
| | PERMITTED TO USE DEMAND FACTORS AS IT IS A 60 AMP |
| | PANEL. PANEL B IS NOT PERMITTED TO USE DEMAND FACTORS |
| | AS IT IS A 60 AMP PANEL. PANEL A SHOWS VALUES FOR |
| | AC/AHU THAT CONFLICT WITH WHAT IS LISTED IN CIRCUIT |
| | DESCRIPTION. NEC 215.2, 220.82, 408.30; FBC RE E3602.2 |
| | 6. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE |
| | OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING |
| | UNIT. NEC 210.52(E)(3); FBC RE E3901.7 |
| | 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC |
| | 210.52; FBC RE E3901.2.1 |
| | 8. BE ADVISED THAT GENERATORS AND SWIMMING POOLS ARE |
| | NOT INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE |
| | A BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS |
| | AND PLAN SUBMITTALS FOR THESE SYSTEMS. WPB FBC 105.1, |
| | 107.2.1 |
| | 9. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI PROTECTED. |
| | PROVIDE CORRECTION. NEC 680.21(C); FBC RE E4203.1.3 |
| | 10. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| | OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER. |
| | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 |
| | 11. ALL 120 VOLT RECEPTACLE OUTLETS INSTALLED IN |
| | LAUNDRY AREAS SHALL HAVE GFCI AND AFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8(A)(9), 210.12(A); FBC RE |
| | E3902.9, 3902.16 |
| | 12. PANEL P APPEARS TO NOT HAVE THE CLEARANCE REQUIRED |
| | PER CODE. PROVIDE CORRECTION. NEC 110.26; FBC RE |
| | E3405.1 |
| | 13. PLAN DOES NOT SHOW THE LOCATION OF ATS SHOWN ON |
| | RISER DIAGRAM. PROVIDE CORRECTION. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |