 FIRST REVIEW
  
 PERMIT APPLICATION #18060620
  
 CODE IN EFFECT
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 NOTE THE DESIGNER OF RECORD HAS ELECTED TO DEFER THE
 SUBMITTAL OF THE FOLLOWING PRODUCTS:
  
 A) WINDOWS/DOORS
 B) STAIRS
 C) RAILS
 D) ROOFING
  
 PLEASE NOTE THE PROPERTY CONTROL NUMBER(PCN) ON
 APPLICATION HAS BEEN CORRECTED. THE PCN FOR 120 SUMMA
 IS 74-43-44-10-15-000-0320.
  
 PLEASE PROVIDE OR MAKE THE FOLLOWING CORRECTIONS:
  
 1. PLEASE CORRECT THE COVER PAGE TO INDICATE THE
 APPLICABLE CODE IN EFFECT.
 2. [FBC R107.2.5]PROVIDE SURVEY OF PROPERTY. SURVEY TO
 INCLUDE EASEMENTS LOCATED ON PROPERTY.
 3. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN. TO COMPLY
 WITH [FBC R401.3]. THE CURRENT SHEET C1 WOULD NOT MEET
 DRAINAGE REQUIREMENTS. WHERE DOES TRENCH DRAIN RELEASE?
 CONSIDER HOW TO UTILIZE SCUPPERS, GUTTERS AND DRAINS TO
 MANAGE WATER WITHIN SITE AND DRAIN TO SANITARY SEWER
 INLETS.
  
 4. THE CITY OF WPB HAS ADOPTED A 2' FREEBOARD ABV. BASE
 FLOOD ELEVATION. THIS PROPERTY HAVE A BASE FLOOD
 ELEVATION OF 6' NAVD88. THAT WOULD PUT YOUR LOWEST
 FLOOR LEVEL AT 8' NAVD88. PLEASE ADJUST YOUR ELEVATIONS
 AND EXPRESS IN NAV88, NOT NGVD ON SHEET A-0.1 & C1.
 GARAGE CAN BE LOWER THAN 8' NAVD88 WITH THE FLOOD DRAIN
 LOUVERS AS SPECIFIED ON SHEET A-1.0
 4.(B) FBC 107.3.5.3.1 PROVIDE A FLOOD ELEVATION
 CERTIFICATE WITH DESIGN FLOOD ELEVATIONS TO INCLUDE ANY
 MECHANICAL EQUIPMENT AS APPLICABLE.
 5. [FBC R903.4]PROVIDE ROOF DRAINAGE CALCULATION AND
 SCUPPERS DETAIL TO COMPLY.
 6. [FBC R401.4]PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY.
 7. [FBC R506.2.3] A 6-MIL POLYETHYLENE OR APPROVED
 VAPOR RETARDER WITH JOINTS LAPPED NOT LESS THAN 6
 INCHES. UPDATE NOTE ON S-1 TO REQUIRE 6 MIL.
  
 10. [FBC R301.2.1]PROVIDE METHOD USED TO DETERMINE
 OPENING PRESSURES. SHOW PRESSURES AT EACH OPENING ON
 ELEVATION SHEETS OR DOOR/WINDOW SCHEDULES (INCLUDE END
 ZONES AS APPLICABLE).
  
 ALTHOUGH THE DESIGNER HAS ELECTED TO DEFER PRODUCT
 APPROVALS, PLEASE NOTE THE BELOW:
 11. SUBMITTED N.O.A. NO.16-0808.11 IS FOR GARAGE DOORS
 UP TO 14'-2" WIDE. PLEASE PROVIDE PRODUCT APPROVAL FOR
 16' WIDE GARAGE DOOR AS SHOWN ON DOOR SCHEDULE.
  
 PLEASE STAMP ALL PRODUCT APPROVALS AS REVIEWED, LIST
 NOA'S ON PLANS OR CREATE 8 1/2 X 11 REVIEW SHEET TO
 LIST ALL NOA'S ON PROJECT.
  
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  
  
  