| 2018-10-11 08:08:11 | PLAN |
| | REVIEW COMMENTS |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | 1) THE ENTRY DOOR FOR THIS PROJECT IS A CUSTOM DOOR AND |
| | APPARENTLY DOES NOT HAVE A PRODUCT APPROVAL AS REQUIRED |
| | BY FAC RULE 61G20-3. THEREFORE, YOU ARE REQUIRED TO |
| | COMPLY WITH THE FOLLOWING. |
| | FBC-R612.2 PERFORMANCE. |
| | EXTERIOR WINDOWS AND DOORS SHALL BE DESIGNED TO RESIST |
| | THE DESIGN WIND LOADS SPECIFIED IN TABLE R301.2(2) |
| | ADJUSTED FOR HEIGHT AND EXPOSURE IN ACCORDANCE WITH |
| | TABLE FBC-R301.2(3). FOR TESTING REQUIRED IN SECTIONS |
| | R612.3 AND R612.5, DESIGN PRESSURES DETERMINED FROM |
| | TABLE R301.2(2) OR ASCE 7 ARE PERMITTED TO BE |
| | MULTIPLIED BY 0.6. |
| | |
| | FBC-R612.2.1 CUSTOM DOORS. |
| | CUSTOM (ONE-OF-A-KIND) EXTERIOR DOOR ASSEMBLIES SHALL |
| | BE TESTED BY AN APPROVED TESTING LABORATORY OR BE |
| | ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING |
| | PRACTICES. |
| | |
| | FBC-R612.3.1 COMPARATIVE ANALYSIS. |
| | STRUCTURAL WIND LOAD DESIGN PRESSURES FOR WINDOW AND |
| | DOOR UNITS OTHER THAN THE SIZE TESTED IN ACCORDANCE |
| | WITH SECTION R612.3 SHALL BE PERMITTED TO BE DIFFERENT |
| | THAN THE DESIGN VALUE OF THE TESTED UNIT PROVIDED SUCH |
| | DIFFERENT PRESSURES ARE DETERMINED BY ACCEPTED |
| | ENGINEERING ANALYSIS OR VALIDATED BY AN ADDITIONAL TEST |
| | OF THE WINDOW OR DOOR UNIT TO THE DIFFERENT DESIGN |
| | PRESSURE IN ACCORDANCE WITH SECTION R612.3. ALL |
| | COMPONENTS OF THE ALTERNATIVE SIZE UNIT SHALL BE THE |
| | SAME AS THOSE OF THE TESTED OR LABELED UNIT. |
| | |
| | |