2019-06-11 16:07:46BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 5TH REVIEW BY THIS PLANS EXAMINER
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE COVER PAGE PER FBC R CHPT3 - BUILDING
 PLANNING. INCLUDE THE FOLLOWING: (SEE ITEM K ) 3RD
 REQUEST - CORRECTED
  
 K. FINISHED FLOOR ELEVATION - (R403.1.7.3 FOUNDATION
 ELEVATION.CORRECTED - FINISH FLOOR ELEVATION HAS BEEN
 ESTABLISHED AT 12.0 FEET.
  
 2. PROVIDE SITE DRAINAGE PLAN - CORRECTED
 FBC R401.3 SITE DRAINAGE
  
 3. VALUE - (ADJUSTED TO $551,070.00) (CORRECTED)
  
 NOTE: APPLICANT MAY PETITION ROBERT BROWN, B.O. FOR
 ADJUSTMENT TO VALUE.
  
 4. PROVIDE ENERGY SUBMITTAL - CORRECTED (U-FACTORS FOR
 GLAZING TO BE VERIFIED IN FIELD)
 (BUILDER TO SIGN EPL CARD, OWNER/AGENT TO SIGN ENERGY
 SUBMITTAL)
  
 5. PROVIDE WINDOW AND DOOR SCHEDULE. - NOT ADDRESSED -
 4TH REQUEST (DESIGN PRESSURES MAY BE PLACED ON PLANS
 NEXT TO EACH OPENING IN LIEU OF WINDOW AND DOOR
 SCHEDULE)
  
 R301.2.1 WIND DESIGN CRITERIA. (PROVIDE DESIGN
 PRESSURES FOR EACH OPENING)
  
 6. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS. -
 NOT ADDRESSED - 4TH REQUEST (SEE OPTION BELOW)
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 (107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.)
  
  
 7. OK
  
 8. REFERENCE BOLT TENSIONING NOTE ON PLAN PAGE 009, 1
 OF 17. BOLTS ARE TO BE INSTALLED PER TURN OF THE NUT
 METHOD. THIS INDICATES THE STRUCTURAL CONNECTIONS ARE
 SLIP CRITICAL AND WILL REQUIRED A (THIRD PARTY
 INSPECTOR) TO VERIFY BOLT INSTALLATION.
 (SEE THRESHOLD REVIEW COMMENTS) 4TH REQUEST
  
 9. PROVIDE SHOP DRAWINGS FOR SPIRAL STAIRCASE. (
 REMOVED FROM PLAN )
  
 NEW COMMENTS
  
 10. PLAN PAGES 008 THRU 025 FOR PRE-ENGINEERD METAL
 BUILDING HAVE BEEN REVIEWED AND APPROVED. SIGNATURE AND
 SEAL OF DESIGN PROFESSIONAL HAS BEEN VERIFIED. (SEE
 SIGNATURE REVIEW COMMENTS)
  
 11. PROVIDE FOUNDATION PLAN. CORRECTED
  
 12. PROVIDE CONNECTION DETAIL FOR INTERIOR STAIRCASES.
 CORRECTED
  
 13. REFERENCE PLAN PAGE A-1. CORRECT GOVERNING CODE TO
 6TH ED 2017. CORRECTED
  
 14. SPECIFY WHAT TYPE OF INSULATION WILL BE INSTALLED
 TO OBTAIN REQUIRED R VALUE.
  
 15. IN THE SUPPORTING DOCUMENTS THERE ARE SEVERAL
 DUPLICATE PLAN PAGES. PLEASE REMOVE ANY DUPLICATE PAGES
 IN PROJECT DOX.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 EXPIDITED PLAN REVIEW FEES WILL BE ASSESSED.
  
 ADDITIONAL FEES MAY APPLY AS FOLLOWS:
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
  
  