| 2019-06-12 12:35:38 | PLUMBING 6TH REVIEW**DENIED** |
| | |
| | |
| | NOTE***PER FL ST 553.80 (B)2B WITH RESPECT TO |
| | EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW.*** |
| | |
| | |
| | PREVIOUS COMMENTS NOT ADDRESSED: |
| | |
| | 2) SHOW ACCESS TO THE WASHING MACHINE VALVES LOCATED |
| | BEHIND THE MACHINE.FBC-RES P2903.9.3 PLACE NOTE ON PLAN |
| | |
| | 3) PROVIDE MANUFACTURE INSTALLATION MANUAL FOR THE |
| | WATER HEATERS BEING USED. PLACE NOT ON PLAN WATER |
| | HEATER SHALL COMPLY WITH FBC RES P2801.2, P2801.6, |
| | P2801.6.2, P2804.6.1 DETAIL SHOWN ON PLAN DOES NOT |
| | COMPLY WITH CODE PLEASE CORRECT OR REMOVE FROM PLAN. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4) SHOW HAMMER ARRESTOR BEING USED AT ALL QUICK CLOSING |
| | VALVES. FBC-RES P2903.5 |
| | REQUIRED ON HOT PIPING FOR DISHWASHER AND CLOTHES |
| | WASHING MACHINE SHOW ON WATER ISOMETRIC. ARRESTORS NOT |
| | SHOWN ON HOT PIPING PLEASE SHOW ARRESTOR ON HOT AND |
| | COLD PIPING FOR DISHWASHER AND CLOTHES WASHING MACHINE. |
| | PER FBC RES P2903.5 |
| | |
| | 5.) THE 2" WATER SERVICE REQUIRES A RPZ BACKFLOW DEVISE |
| | WITH A SEPARATE PERMIT. PER WPB UTILITIES DEPARTMENT. |
| | ON THE PLUMBING SITE LATOUT SHEET IT SHOWS A 2" WATER |
| | SERVICE PLACE NOTE ON THE PLAN RPZ BACKFLOW REQUIRED |
| | WITH SEPARATE PERMIT. PLACE NOTE ON PLAN RPZ SHALL BE |
| | INSTALLED NEXT TO METER AND SHALL HAVE SEPARATE PERMIT. |
| | |
| | NEW COMMENTS; |
| | |
| | 1. THE VENTS FOR THE TOILETS AND THE TUBS ARE SHOWN AS |
| | HORIZONTAL DRY VENT WHICH ARE NOT ALLOWED PER FBC RES |
| | P3104.3, P3104.4 THE CORRECT WAY OF VENTING THE |
| | BATHROOM GROUP IS TO CONNECT THE BRANCH DRAIN OF THE |
| | LAVATORY TO THE BUILDING DRAIN BETWEEN THE TOILET AND |
| | TUB THE VENT ON THE LAVATORY WILL VENT THE BATHROOM |
| | GROUP MAKING IT A HORIZONTAL WET VENT SYSTEM. PER FBC |
| | RES P3108.4 |
| | |
| | 2. FIXTURES CAN NOT BE DOUBLE TRAPPED THE PLAN SHOWS |
| | THE LAVATORY AND TUB CONNECTING TO THE FLOOR DRAIN |
| | TRAPS TH IS NOT ALLOWED THE BRANCH DRAINS FROM THE |
| | LAVATORY AND TUB SHALL BE CONNECTED SEPARATELY TO THE |
| | BUILDING DRAIN. PER FBC RES P3201.6 |
| | |
| | 3. THE KITCHEN DRAIN SHALL NOT CONNECT TO THE BATHROOM |
| | GROUP IT SHALL CONNECT TO THE BUILDING DRAIN DOWN STEAM |
| | OF THE BATHROOM GROUP. PER FBC RES FBC RES P3108.4 |
| | |