2019-06-12 12:35:38PLUMBING 6TH REVIEW**DENIED**
  
  
 NOTE***PER FL ST 553.80 (B)2B WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.***
  
  
 PREVIOUS COMMENTS NOT ADDRESSED:
  
 2) SHOW ACCESS TO THE WASHING MACHINE VALVES LOCATED
 BEHIND THE MACHINE.FBC-RES P2903.9.3 PLACE NOTE ON PLAN
  
 3) PROVIDE MANUFACTURE INSTALLATION MANUAL FOR THE
 WATER HEATERS BEING USED. PLACE NOT ON PLAN WATER
 HEATER SHALL COMPLY WITH FBC RES P2801.2, P2801.6,
 P2801.6.2, P2804.6.1 DETAIL SHOWN ON PLAN DOES NOT
 COMPLY WITH CODE PLEASE CORRECT OR REMOVE FROM PLAN.
 PER WPB AMEND TO FBC 107.2.1
  
 4) SHOW HAMMER ARRESTOR BEING USED AT ALL QUICK CLOSING
 VALVES. FBC-RES P2903.5
 REQUIRED ON HOT PIPING FOR DISHWASHER AND CLOTHES
 WASHING MACHINE SHOW ON WATER ISOMETRIC. ARRESTORS NOT
 SHOWN ON HOT PIPING PLEASE SHOW ARRESTOR ON HOT AND
 COLD PIPING FOR DISHWASHER AND CLOTHES WASHING MACHINE.
 PER FBC RES P2903.5
  
 5.) THE 2" WATER SERVICE REQUIRES A RPZ BACKFLOW DEVISE
 WITH A SEPARATE PERMIT. PER WPB UTILITIES DEPARTMENT.
 ON THE PLUMBING SITE LATOUT SHEET IT SHOWS A 2" WATER
 SERVICE PLACE NOTE ON THE PLAN RPZ BACKFLOW REQUIRED
 WITH SEPARATE PERMIT. PLACE NOTE ON PLAN RPZ SHALL BE
 INSTALLED NEXT TO METER AND SHALL HAVE SEPARATE PERMIT.
  
 NEW COMMENTS;
  
 1. THE VENTS FOR THE TOILETS AND THE TUBS ARE SHOWN AS
 HORIZONTAL DRY VENT WHICH ARE NOT ALLOWED PER FBC RES
 P3104.3, P3104.4 THE CORRECT WAY OF VENTING THE
 BATHROOM GROUP IS TO CONNECT THE BRANCH DRAIN OF THE
 LAVATORY TO THE BUILDING DRAIN BETWEEN THE TOILET AND
 TUB THE VENT ON THE LAVATORY WILL VENT THE BATHROOM
 GROUP MAKING IT A HORIZONTAL WET VENT SYSTEM. PER FBC
 RES P3108.4
  
 2. FIXTURES CAN NOT BE DOUBLE TRAPPED THE PLAN SHOWS
 THE LAVATORY AND TUB CONNECTING TO THE FLOOR DRAIN
 TRAPS TH IS NOT ALLOWED THE BRANCH DRAINS FROM THE
 LAVATORY AND TUB SHALL BE CONNECTED SEPARATELY TO THE
 BUILDING DRAIN. PER FBC RES P3201.6
  
 3. THE KITCHEN DRAIN SHALL NOT CONNECT TO THE BATHROOM
 GROUP IT SHALL CONNECT TO THE BUILDING DRAIN DOWN STEAM
 OF THE BATHROOM GROUP. PER FBC RES FBC RES P3108.4
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711