| 2019-06-13 09:30:09 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: 6TH REVIEW, DENIED, SEE |
| | COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. RISER DIAGRAM PROVIDED BUT NEEDS CORRECTIONS. SEE |
| | NEW COMMENTS. |
| | 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. NEC 220; FBC RE E3602.2 (6TH REVIEW: LOAD |
| | CALCULATION IS NOT ACCURATE, SEE PREVIOUS COMMENTS.) |
| | 3. PANEL SCHEDULES PROVIDED BUT NOT CORRECT. SEE |
| | COMMENTS BELOW. |
| | 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902 |
| | (6TH REVIEW: NOT PROVIDED.) |
| | 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| | NEC 110.3, 110.9; FBC RE E3606.3 (6TH REVIEW, AIC |
| | RATING OF ELECRTICAL EQUIPMENT STILL NOT PROVIDED.) |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 (6TH |
| | REVIEW: NOT PROVIDED.) |
| | 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 (6TH |
| | REVIEW: NOT PROVIDED.) |
| | 11. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 |
| | (6TH REVIEW: NOT PROVIDED.) |
| | 12. A MINIMUM OF TWO 20 AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY KITCHEN COUNTERTOP RECEPTACLE |
| | OUTLET(S). PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC |
| | RE E3703.2 (6TH REVIEW: NOT PROVIDED. IN ADDITION, THE |
| | 20 AMP SMALL APPLIANCE CIRCUITS SHALL HAVE NO OTHER |
| | OUTLETS. NEC 210.52(B)(2)) |
| | 13. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS |
| | FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS |
| | SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE |
| | IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A |
| | RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES |
| | NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION. |
| | NEC 210.52(C)(1); FBC RE E3901 (5TH REVIEW: NOT |
| | CORRECTED.) |
| | 14. PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE |
| | LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC |
| | 210.52(F); FBC RE E3901.8 (6TH REVIEW: NOT TO CODE.) |
| | 15. CORRECTED. |
| | 16. CORRECTED. |
| | 17. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB |
| | FBC 107.2.1 (6TH REVIEW: NOT PROVIDED COMPLETELY. WHERE |
| | IS THE METER CAN LOCATED? SHOW ON PLAN.) |
| | 18. CORRECTED. |
| | 19. CORRECTED. |
| | 20. CORRECTED. |
| | 21. CORRECTED. |
| | 22. CORRECTED. |
| | 23. LOAD CALCULATION DOES NOT MATCH THE METHOD IN FBC |
| | RESIDENTIAL OR THE NEC, WHICHEVER WOULD APPLY DEPENDING |
| | ON SERVICE TYPE. PROVIDE A RESIDENTIAL LOAD CALCULATION |
| | THAT INCLUDES ALL LOADS AND DEMAND FACTORS AS |
| | PERMITTED. PROVIDE ACCURATE LOAD CALCULATION INCLUDING |
| | ALL LOADS TO MATCH THE TYPE OF SERVICE. NEC 220; FBC RE |
| | E3602.2 (6TH REVIEW, NOT PROVIDED ACCURATELY.) |
| | 24. CORRECTED. |
| | 25. CORRECTED. |
| | 26. CORRECTED. |
| | 27. PANEL SCHEDULES SHOW 10 GAUGE WIRE ON A 32 AMP |
| | BREAKER IN SEVERAL LOCATIONS. THIS IS NOT A STANDARD |
| | BREAKER SIZE, AND THE WIRE SIZE IS NOT PERMITTED TO BE |
| | USED ON A BREAKER OVER 30 AMPS. PROVIDE CORRECTION. NEC |
| | 240.4(D), 240.6, 310.15(B)(16) (NOT CORRECTED.) |
| | 28. NEW PLAN SHEETS SUBMITTED HAVE THE SAME NAME: |
| | EL-100.01. PLAN SHEETS NEED TO HAVE DISTINCT NAMES. |
| | PROVIDE CORRECTION. WPB FBC 107.2.1 (NOT CORRECTED.) |
| | 29. PROVIDE SPEC SHEET FOR 32 AMP BREAKER AS THIS IS |
| | NOT A STANDARD SIZE BREAKER. NEC 240.6 (NOT PROVIDED.) |
| | 30. PROVIDE SPEC SHEET FOR 160 AMP BREAKER AS THIS IS |
| | NOT A STANDARD SIZE BREAKER. NEC 240.6 (NOT PROVIDED.) |
| | |
| | END OF COMMENTS. |
| | |
| | BE ADVISED THAT THERE IS A SUBSTANTIAL AMOUNT OF |
| | INFORMATION MISSING ON THE SUBMITTED PLAN. UPON NEXT |
| | REVIEW, FURTHER COMMENTS ARE POSSIBLE. |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |