| 2019-05-08 09:47:53 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 4TH REVIEW BY THIS PLANS EXAMINER |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE COVER PAGE PER FBC R CHPT3 - BUILDING |
| | PLANNING. INCLUDE THE FOLLOWING: (SEE ITEM K ) 3RD |
| | REQUEST |
| | |
| | K. FINISHED FLOOR ELEVATION - (R403.1.7.3 FOUNDATION |
| | ELEVATION. |
| | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION |
| | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER |
| | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED |
| | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 |
| | PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO |
| | THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN |
| | BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF |
| | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT |
| | ALL LOCATIONS ON THE SITE). |
| | |
| | 2. PROVIDE SITE DRAINAGE PLAN - CORRECTED |
| | FBC R401.3 SITE DRAINAGE |
| | |
| | 3. VALUE - (ADJUSTED TO $551,070.00) (CORRECTED) |
| | |
| | NOTE: APPLICANT MAY PETITION ROBERT BROWN, B.O. FOR |
| | ADJUSTMENT TO VALUE. |
| | |
| | 4. PROVIDE ENERGY SUBMITTAL - (U-FACTORS FOR GLAZING TO |
| | BE VERIFIED IN FIELD) |
| | |
| | 5. PROVIDE WINDOW AND DOOR SCHEDULE. - NOT ADDRESSED - |
| | 3RD REQUEST (DESIGN PRESSURES MAY BE PLACED ON PLANS |
| | NEXT TO EACH OPENING IN LIEU OF WINDOW AND DOOR |
| | SCHEDULE) |
| | |
| | R301.2.1 WIND DESIGN CRITERIA. (PROVIDE DESIGN |
| | PRESSURES FOR EACH OPENING) |
| | |
| | 6. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS. - |
| | NOT ADDRESSED - 3RD REQUEST (SEE OPTION BELOW) |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. |
| | |
| | (107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON |
| | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING |
| | OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL.) |
| | |
| | |
| | 7. OK |
| | |
| | 8. REFERENCE BOLT TENSIONING NOTE ON PLAN PAGE 009, 1 |
| | OF 17. BOLTS ARE TO BE INSTALLED PER TURN OF THE NUT |
| | METHOD. THIS INDICATES THE STRUCTURAL CONNECTIONS ARE |
| | SLIP CRITICAL AND WILL REQUIRED A (THIRD PARTY |
| | INSPECTOR) TO VERIFY BOLT INSTALLATION. |
| | (SEE THRESHOLD REVIEW COMMENTS) 3RD REQUEST |
| | |
| | 9. PROVIDE SHOP DRAWINGS FOR SPIRAL STAIRCASE. ( |
| | REMOVED FROM PLAN ) |
| | |
| | NEW COMMENTS |
| | |
| | 10. PLAN PAGES 008 THRU 025 FOR PRE-ENGINEERD METAL |
| | BUILDING HAVE BEEN REVIEWED AND APPROVED. SIGNATURE AND |
| | SEAL OF DESIGN PROFESSIONAL HAS BEEN VERIFIED. (SEE |
| | SIGNATURE REVIEW COMMENTS) |
| | |
| | 11. PROVIDE FOUNDATION PLAN. CORRECTED |
| | |
| | 12. PROVIDE CONNECTION DETAIL FOR INTERIOR STAIRCASES. |
| | CORRECTED |
| | |
| | 13. REFERENCE PLAN PAGE A-1. CORRECT GOVERNING CODE TO |
| | 6TH ED 2017. CORRECTED |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | EXPIDITED PLAN REVIEW FEES WILL BE ASSESSED. |
| | |
| | ADDITIONAL FEES MAY APPLY AS FOLLOWS: |
| | F.S. 553.80 (2) (B) |
| | (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | |
| | |