2019-05-02 10:58:25PLUMBING 5TH REVIEW**DENIED**
  
  
 NOTE***PER FL ST 553.80 (B)2B WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.***
  
  
 PREVIOUS COMMENTS NOT ADDRESSED:
  
 1) WASHING MACHINES SHALL NOT DISCHARGE INTO THE
 HORIZONTAL WET VET OF THE BATHROOM GROUP FIXTURE'S. FBC
 RES P3108.1
  
 2) SHOW ACCESS TO THE WASHING MACHINE VALVES LOCATED
 BEHIND THE MACHINE.FBC-P 604.10.3
  
 3) PROVIDE INSTALLATION MANUAL FOR THE WATER HEATERS
 BEING USED. FBC 107.1
  
 4) SHOW HAMMER ARRESTOR BEING USED AT ALL QUICK CLOSING
 VALVES. FBC-RES P2903.5
 REQUIRED ON HOT PIPING FOR DISHWASHER AND CLOTHES
 WASHING MACHINE SHOW ON WATER ISOMETRIC.
  
 5.) THE 2" WATER SERVICE REQUIRES A RPZ BACKFLOW DEVISE
 WITH A SEPARATE PERMIT. PER WPB UTILITIES DEPARTMENT.
 ON THE PLUMBING SITE LATOUT SHEET IT SHOWS A 2" WATER
 SERVICE PLACE NOTE ON THE PLAN RPZ BACKFLOW REQUIRED
 WITH SEPARATE PERMIT
  
 6). THE WASHING MACHINES REQUIRE HOT WATER. PER FBC PL
 607.1
  
 NEW COMMENTS;
  
 1) FIXTURES ARE NOT VENTED EACH FIXTURE SHALL BE VENTED
 OR CONNECTED TO A VENTED LINE THE KITCHEN AND WASHING
 MACHINE SHALL BE VENTED SEPARATELY THE CANNOT CONNECT
 TO THE BATHROOM GROUP. PER FBC RES P3101.2.1
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER