Plan Review Notes For Permit 18060580
Permit Number 18060580
Review Stop P
Sequence Number 4
Notes
Date Text
2019-04-10 16:15:12PLUMBING 3RD REVIEW**DENIED**
  
  
 NOTE***PER FL ST 553.80 (B)2B WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.***
  
  
 PREVIOUS CMMENTS NOT ADDRESSED:
  
 1) DIGITAL PLANS SHALL COMPLY WITH 61G15-23.003 AND BE
 ELECTRONICALLY SIGNED ON ELECTRONICALLY TRANSMITTED
 PLANS. SOME PLANS ARE NOT SIGNED AT ALL.
  
 2) EVERY TOILET AND TUB ARE DRY VENTED. DRY VENTING OF
 FIXTURES ARE NOT PERMITTED AND MUST COMPLY WITH FBC-P
 912.2, 912.2.1, 912.2.2.
  
 3) WASHING MACHINES SHALL NOT DISCHARGE INTO THE
 HORIZONTAL WET VET OF THE BATHROOM GROUP FIXTURE'S.
 FBC-P 912.1
  
 4) FITTING ON FLAT DRAWING APPEAR TO BE SANITARY TEE'S
 WHICH ARE NOT PERMITTED FOR USE ON THERE BACK OR SIDE
 FOR DRAINAGE. FBC-P 706.3
  
 5) THE TERM GULLY TRAP IS NOT DEFINED IN THE FBC.
 PLEASE CLARIFY. FBC 107.1
  
 6) MISSING P-TRAPS ON FLAT DRAWING. EACH FIXTURE HAS BE
 TRAPPED AND VENTED. FBC-P 1002.1
  
 7) SHOW ACCESS TO THE WASHING MACHINE VALVES LOCATED
 BEHIND THE MACHINE.FBC-P 604.10.3
  
 8)PROVIDE A COMPLETE SANITARY ISOMETRIC. FBC-P 107.3.5
  
 9) PROVIDE INSTALLATION MANUAL FOR THE WATER HEATERS
 BEING USED. FBC 107.1
  
 10) HOT WATER SHALL BE ON THE LEFT SIDE OF ALL
 FIXTURES. FBC-P 607.4
  
 11) SHT.1007 LIST WATER PIPING AS BOT POLYPROPYLENE AND
 UPVC. PLEASE CLEARIFY AS UPVC IS NOT AN APPROVED PIPING
 SYSTEM PER FBC-P 605.4
  
 12) SHOW HAMMER ARRESTOR BEING USED AT ALL QUICK
 CLOSING VALVES. FBC-P 604.9
  
 13) WHY IS THERE AN AIR ADMITTANCE VALVE LOCATED ON THE
 WATER RISER DIAGRAM ON SHT. WS106? PLEASE CLEARIFY IT
 USE. FBC-P 107.1
  
  
 NEW COMMENTS :
  
 1. THE 2" WATER SERVICE REQUIRES A RPZ BACKFLOW DEVISE
 WITH A SEPERATE PERMIT. PER WPB UTILITIES DEPARMENT
 2. THE WASHING MACINES REQUIRE HOT WATER. PER FBC RES
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  