| 2019-03-19 16:02:11 | PLUMBING 3RD REVIEW**DENIED** |
| | |
| | |
| | NOTE***PER FL ST 553.80 (B)2B WITH RESPECT TO |
| | EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW.*** |
| | |
| | |
| | 1) DIGITAL PLANS SHALL COMPLY WITH 61G15-23.003 AND BE |
| | ELECTRONICALLY SIGNED ON ELECTRONICALLY TRANSMITTED |
| | PLANS. SOME PLANS ARE NOT SIGNED AT ALL. |
| | |
| | 2) EVERY TOILET AND TUB ARE DRY VENTED. DRY VENTING OF |
| | FIXTURES ARE NOT PERMITTED AND MUST COMPLY WITH FBC-P |
| | 912.2, 912.2.1, 912.2.2. |
| | |
| | 3) WASHING MACHINES SHALL NOT DISCHARGE INTO THE |
| | HORIZONTAL WET VET OF THE BATHROOM GROUP FIXTURE'S. |
| | FBC-P 912.1 |
| | |
| | 4) FITTING ON FLAT DRAWING APPEAR TO BE SANITARY TEE'S |
| | WHICH ARE NOT PERMITTED FOR USE ON THERE BACK OR SIDE |
| | FOR DRAINAGE. FBC-P 706.3 |
| | |
| | 5) THE TERM GULLY TRAP IS NOT DEFINED IN THE FBC. |
| | PLEASE CLARIFY. FBC 107.1 |
| | |
| | 6) MISSING P-TRAPS ON FLAT DRAWING. EACH FIXTURE HAS BE |
| | TRAPPED AND VENTED. FBC-P 1002.1 |
| | |
| | 7) SHOW ACCESS TO THE WASHING MACHINE VALVES LOCATED |
| | BEHIND THE MACHINE.FBC-P 604.10.3 |
| | |
| | 8)PROVIDE A COMPLETE SANITARY ISOMETRIC. FBC-P 107.3.5 |
| | |
| | 9) PROVIDE INSTALLATION MANUAL FOR THE WATER HEATERS |
| | BEING USED. FBC 107.1 |
| | |
| | 10) HOT WATER SHALL BE ON THE LEFT SIDE OF ALL |
| | FIXTURES. FBC-P 607.4 |
| | |
| | 11) SHT.1007 LIST WATER PIPING AS BOT POLYPROPYLENE AND |
| | UPVC. PLEASE CLEARIFY AS UPVC IS NOT AN APPROVED PIPING |
| | SYSTEM PER FBC-P 605.4 |
| | |
| | 12) SHOW HAMMER ARRESTOR BEING USED AT ALL QUICK |
| | CLOSING VALVES. FBC-P 604.9 |
| | |
| | 13) WHY IS THERE AN AIR ADMITTANCE VALVE LOCATED ON THE |
| | WATER RISER DIAGRAM ON SHT. WS106? PLEASE CLEARIFY IT |
| | USE. FBC-P 107.1 |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER |
| | BUILDING DIVISION |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |