| 2019-01-23 09:54:45 | PERMIT # 18060580 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | 2ND REVIEW - FAIL COMMENTS |
| | |
| | THIS SUBMISSION APPEARS TO BE MISSING SHEETS AND |
| | DETAILS THAT WERE IN THE ORIGINAL SUBMISSION. IT DOES |
| | NOT APPEAR THAT ANY OF THE COMMENTS HAVE BEEN |
| | ADDRESSED. |
| | |
| | 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | 2) THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.3 |
| | OF NFPA 101 FLORIDA EDITION 2015. FOR NON-SEPARATED |
| | MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE |
| | SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO |
| | THE BUILDING. |
| | |
| | 3) SHEET CS1.0: PROVIDE CORRECT NUMBER OF STORIES. |
| | |
| | 4) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY |
| | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF |
| | TRAVEL ETC. |
| | |
| | 5) SHEET F2.01: PROVIDE LOCKING KNOX CAPS ON FIRE |
| | DEPARTMENT CONNECTION. |
| | |
| | 6) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION |
| | SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED DURING PLAN RESUBMISSION. |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |