Plan Review Notes
Plan Review Notes For Permit 18060580
Permit Number 18060580
Review Stop Z
Sequence Number 1
Notes
Date Text
2018-06-26 15:50:026/26/18-FAILED SEE COMMENTS BELOW:
  
 1. MAXIMUM BUILDING HEIGHT IS 30 FT. SECTION 94-75
 (A)(3)
 2. NO PARKING WAS PROVIDED ON THE SITE PLAN. 4 PARKING
 SPACES ARE REQUIRED FOR A DUPLEX.
 3. ARE THERE INTERNAL STAIRS?
 4. WHAT IS THE SETBACKS OF THE EXTERNAL STAIRCASE?
 5. LANDSCAPING SHALL BE PROVIDED AS FOLLOWS:
 1 SHADE TREE FOREACH 1500 SQ. FT. OF OPEN SPACE
 1 FLOWERING TREE FOR EACH 6,000 SQ. FT OF OPEN SPACE
 1 SHURB FOR EACH 500 SQ. FT. OF OPEN SPACE
 GRASS SHALL NOT EXCEED 60 PERCENT OF THE REQUIRED
 LANDSCAPING.
 6. A DETAIL FLOOR PLAN SHALL BE PROVIDED SO STAFF CAN
 UNDERSTAND HOW MANY UNITS ARE BEING PROPOSED.
 7. SEPERATE PERMITS ARE REQUIRED FOR LANDSCAPING,
 PARKING AND CURB CUT.
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]
  
  