| Date |
Text |
| 2018-09-20 06:40:45 | 1) COVER SHEET - DEFINE THE OCCUPANCY OF THE STRUCTURE |
| | IN ACCORDANCE WITH CHAPTER 3 OF THE 2017 |
| | FBC-BUILDING.THE PLAN NOTES THE OCCUPANCY AS "POR" |
| | WHICH IS NOT DEFINE IN THE FBC. CLARIFY. |
| | 2) COVER SHEET - A NOTE ON THE LEFT SIDE OF THE COVER |
| | SHEET REFERS TO THE 2010 FLORIDA BUILDING CODE. REMOVE |
| | THIS NOTE. THE CODE IN EFFECT IS THE 2017 FBC. |
| | 3) SHT.A1.01 - THE BREAK ROOM SINKS AND COUNTERTOPS |
| | SHALL COMPLY WITH THE 2017 FBC-ACCESSIBILITY SECS. |
| | 212.3, 606.1 THROUGH 606.5. SHOW THE REQUIRED CLEAR |
| | FLOOR SPACE FOR THE BREAK ROOM SINKS ON THE PLANS. |
| | 4) INDICATE THE OCCUPANT LOAD OF EACH COMMERCIAL SPACE |
| | ON THE FIRST FLOOR IN ACCORDANCE WITH THE 2017 FBC |
| | TABLE 1004.1.2. |
| | 5) THE DOORS IN THE HANDICAP ACCESSIBLE TOILET ROOMS ON |
| | THE FIRST FLOOR CANNOT SWING INTO THE REQUIRED CLEAR |
| | FLOOR SPACE FOR THE LAVATORY PER THE 2017 FBC-ACCESS. |
| | SEC.603.2.3. |
| | 6) THE CONFIGURATION OF THE FIRST FLOOR PLAN ON SHT. |
| | A1.01 DOES NOT CORRELATE WITH SHT. P1.01. THIS ALSO |
| | OCCURS ON THE ELECTRICAL SHEET E1.02, AND THE |
| | MECHANICAL SHEET M0.01. |
| | 7) THE WATER SUPPLY SHUTOFF VALVES FOR THE STACKED |
| | WASHER/DRYER UNITS THAT ARE LOCATED BEHIND THE UNITS |
| | SHALL BE PROVIDED WITH ACCESS OR THE VALVES SHALL BE |
| | RELOCATED TO PROVIDE ACCESS PER THE 2017 FBC-PLUMBING |
| | SEC.606.3. |
| | 8) SHT. A1.02. - SUBMIT STORM DRAIN PIPING CALCULATIONS |
| | IN ACCORDANCE WITH THE 2017 FBC-PLUMBING SECS. L106.2, |
| | 1106.3, 1106.4. |
| | 9) SECONDARY ( EMERGENCY) ROOF DRAINS OR SCUPPERS SHALL |
| | BE PROVIDED FOR THE ROOF PER 2017 FBC-PLUMBING |
| | SEC.1108.1. SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE |
| | END POINT OF DISCHARGE SEPARATE FROM THE PRIMARY |
| | SYSTEM. 2017 FBC-PLUMBING SEC. 1108.2. |
| | 10) SHOW THE OCCUPANT LOAD FOR THE ROOF DECK / |
| | RECREATIONAL ROOM. FBC 107.2.1. |
| | 11) TEMPERED WATER IS REQUIRED TO ALL THE TOILET ROOM |
| | LAVATORIES TO BE USED BY THE PUBLIC, CUSTOMERS, PATRONS |
| | AND GUESTS PER THE 2017 FBC-PLUMBING SEC.416.5. |
| | TEMPERED WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | 12) HOT WATER SHALL BE SUPPLIED TO ALL BREAKROOM SINKS |
| | ON THE FIRST FLOOR. 2017 FBC-PLUMBING SEC.607.1. |
| | 13) THE HOT WATER RECIRCULATION LINE SHALL BE INSULATED |
| | IN ITS ENTIRETY PER THE 2017 FBC-PLUMBING SEC. 607.5 & |
| | 2017 FBC-ENERGY SEC.R403.5.3.MINIMUM WALL THICKNESS |
| | SHALL BE ONE INCH. |
| | 14) THE FIRST FLOOR PLAN ON SHT. P2.01 DOES NOT |
| | CORRELATE WITH THE FIRST FLOOR PLAN ON SHT. A1.01. |
| | CLARIFY. |
| | 15) THE FIRST FLOOR WATER RISER ON P3.01 DOES NOT |
| | CORRELATE WITH THE FIRST FLOOR PLAN ON SHT. A1.01 FOR |
| | THE TYPE OF PLUMBING FIXTURES AND AMOUNT. CLARIFY. |
| | 16) SHT. P3.02 - THE WASTE AND VENT RISER DIAGRAM FOR |
| | THE FIRST FLOOR DOES NOT CORRELATE WITH THE THE FIRST |
| | FLOOR PLAN ON SHT.A1.01 FOR THE TYPE OF PLUMBING |
| | FIXTURES AND AMOUNT. CLARIFY. |
| | 17.)THE BUILDING APPEARS TO BE OVER THREE STORIES, |
| | THEREFORE AN ELEVATOR WILL BE REQUIRED PER FL. STATUTE |
| | 399.305 (2). |
| | 18) SUBMIT COMPLETE DETAILS FOR THE ACCESSIBLE TOILET |
| | ROOMS ON THE FIRST FLOOR.COMPLY WITH 2017 |
| | FBC-ACCESSIBILITY. DETAILS REQUIRED FOR GRAB BARS ( |
| | HEIGHT, LOCATIONS, LENGTHS, ETC.), PLUMBING FIXTURE, |
| | TOILET PAPER AND HAND TOWEL DISPENSERS, MIRRORS, ETC. |
| | 2017 FBC 107.2.1. |
| | 19) IF AN ELEVATOR IS INSTALLED IN THIS BUILDING THEN |
| | ALL THE RESIDENTIAL UNITS SHALL COMPLY WITH ALL THE |
| | REQUIREMENTS OF THE FEDERAL FAIR HOUSING ACT & |
| | GUIDELINES. |
| | 20) SUBMIT FIRESTOPPING DETAILS FOR THE HORIZONTAL AND |
| | VERTICAL PIPE PENETRATIONS. SUBMIT MANUFACTURER'S |
| | INFORMATION, LISTING, INSTALLATION DETAILS, ETC. FBC |
| | 107.2.1. |
| | 21) BACKFLOW PREVENTION DEVICES ARE REQUIRED ON THE |
| | DOMESTIC WATER SERVICE AND THE FIRE SERVICE LINES. A |
| | SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW DEVICES. A |
| | FIRE PROTECTION CONTRACTOR LICENSED AS A CONTRACTOR I, |
| | II OR V SHALL APPLY FOR THE PERMIT FOR THE FIRE |
| | BACKFLOW AND A LICENSED PLUMBING CONTRACTOR SHALL APPLY |
| | FOR DOMESTIC BACKFLOW. PLEASE CONTACT THE CITY OF WPB |
| | UTILITIES DEPT. AT 561-822-2240 FOR THE TYPE OF DEVICE |
| | REQUIRED AND LOCATION. |
| | 22) THE FLOOR DRAINS ON THE FOURTH FLOOR ARE NOT |
| | PROPERLY VENTED. 2017 FBC-PLUMBING SEC.901.2, 901.2.1. |
| | 23) VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH SHALL |
| | BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE ENTIRE |
| | DEVELOPED LENGTH OF THE VENT PIPE. 2017 FBC-PLUMBING |
| | SEC.906.2. |
| | 24) SHT. P4.01 - VENT INCREASER DETAIL - NOTE #1 STATES |
| | "VENT THROUGH ROOF TO BE 4 INCHES." THE SANITARY RISER |
| | ON SHT. P3.02 SHOWS ALL 2 INCH VENTS. CLARIFY. |
| | 25) SHT.P4.01 - SHOW THE SIZE OF THE EXPANSION TANK. |
| | 26) THE MINIMUM SIZE OF THE PAN DRAIN FOR THE WATER |
| | HEATER SHALL BE 3/4 INCH. 2017 FBC-PLUMBING SEC. |
| | 504.7.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |