| 2018-09-13 15:14:58 | PERMIT # 18060580 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | 2) THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. | | | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE | | | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.3 | | | OF NFPA 101 FLORIDA EDITION 2015. FOR NON-SEPARATED | | | MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE | | | SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO | | | THE BUILDING. | | | | | | 3) SHEET CS1.0: PROVIDE CORRECT NUMBER OF STORIES. | | | | | | 4) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY | | | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, | | | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF | | | TRAVEL ETC. | | | | | | 5) SHEET F2.01: PROVIDE LOCKING KNOX CAPS ON FIRE | | | DEPARTMENT CONNECTION. | | | | | | 6) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE | | | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION | | | SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS | | | MAY BE GENERATED DURING PLAN RESUBMISSION. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|