| 2018-06-29 13:15:38 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. |
| | |
| | 1. RISER DIAGRAM SHOWS 1/0 WIRE FROM METER CAN TO |
| | INTERIOR PANEL WITH 125 AMP FUSES IN THE DISCONNECT. |
| | THE CALCULATED LOAD ON THE PANEL OF 172 AMPS EXCEEDS |
| | THE FUSE RATINGS AND THE RATING OF THE WIRE. THIS WAS |
| | MISSED ON THE ORIGINAL PLAN REVIEW, BUT NEEDS TO BE |
| | CORRECTED. PROVIDE CORRECTION. NEC 310.15(B)(16), |
| | 408.30 (PLAN SHOWS SIZE 1/0 WIRE ON A 200 AMP FEEDER. |
| | THIS WIRE IS NOT RATED FOR 200 AMPS AND MUST BE |
| | INCREASED TO A MINIMUM OF 3/0 WITH A #6 EGC PER CODE. |
| | PROVIDE CORRECTION.) |
| | 2. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |