2018-06-29 13:15:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES.
  
 1. RISER DIAGRAM SHOWS 1/0 WIRE FROM METER CAN TO
 INTERIOR PANEL WITH 125 AMP FUSES IN THE DISCONNECT.
 THE CALCULATED LOAD ON THE PANEL OF 172 AMPS EXCEEDS
 THE FUSE RATINGS AND THE RATING OF THE WIRE. THIS WAS
 MISSED ON THE ORIGINAL PLAN REVIEW, BUT NEEDS TO BE
 CORRECTED. PROVIDE CORRECTION. NEC 310.15(B)(16),
 408.30 (PLAN SHOWS SIZE 1/0 WIRE ON A 200 AMP FEEDER.
 THIS WIRE IS NOT RATED FOR 200 AMPS AND MUST BE
 INCREASED TO A MINIMUM OF 3/0 WITH A #6 EGC PER CODE.
 PROVIDE CORRECTION.)
 2. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  