| 2018-06-20 15:03:36 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. RISER DIAGRAM SHOWS 1/0 WIRE FROM METER CAN TO | | | INTERIOR PANEL WITH 125 AMP FUSES IN THE DISCONNECT. | | | THE CALCULATED LOAD ON THE PANEL OF 172 AMPS EXCEEDS | | | THE FUSE RATINGS AND THE RATING OF THE WIRE. THIS WAS | | | MISSED ON THE ORIGINAL PLAN REVIEW, BUT NEEDS TO BE | | | CORRECTED. PROVIDE CORRECTION. NEC 310.15(B)(16), | | | 408.30 | | | 2. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN THAT | | | IS READILY ACCESSIBLE. NEC 422.5, 422.52 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|