| 2018-11-06 10:03:49 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18060562 |
| | 11/6/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) CORRECT THE ENERGYGAUGE COMPLIANCE FORM WHICH IS |
| | SPECIFYING THE JURISDICTION AS ALACHUA COUNTY FL. ON |
| | PAGE 2. |
| | |
| | 2) 2ND REQUEST FOR THE MANUFACTURER'S PRODUCT DATA |
| | (CUT) SHEETS FOR THE GAS-FIRED COOKING APPLIANCES. |
| | THESE SUBMITTAL DOCUMANTS CAN BE DEFERRED IF REQUESTED |
| | BY THE DESIGN PROFESSIONAL, HOWEVER ENGINEER STAMPED |
| | COPIES WILL HAVE TO BE SUBMITTED PRIOR TO INSPECTION TO |
| | AVOID A FAILURE IN THE FIELD. |
| | |
| | 3) THE AIR BALANCE INDICATES ALL 2000 CFMS OF O/A FROM |
| | RTU-1 IS DEDICATED TO THE RESTROOMS, HOWEVER THE |
| | COMBUSTION AIR CALCULATION FOR THE KITCHEN INDICATES |
| | THAT 750 CFMS OF O/A FROM THE UNIT WILL BE PROVIDED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |