| 2018-12-11 15:48:13 | 2ND REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PREVIOUS GAS COMMENTS: |
| | |
| | 1. NOT COMPLIED SHT. P5.1 UNDER THE GAS NOTES #5 IT IS |
| | REFERENCING A 5LB TO 1/2LB REGULATOR AT EACH APPLIANCE |
| | IS THIS A 5LB SYSTEM PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 SHT WAS CHANGED TO P6.1 NOTE #6 |
| | |
| | 2.NOT COMPLIED PLEASE INDICATE SYSTEM PRESSURE ON THE |
| | RISER. PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| | |
| | 3.NOT COMPLIED SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (GAS METER / MP REGULATOR / LP TANK) TO THE |
| | MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER |
| | THE 2017 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 |
| | FBC-RES. SEC. G 2413.4.1, G2413.4.2. SHOW METER ON |
| | RISER RESPONSE LETTER STATED IT WAS SHOWN ON CIVIL I |
| | COULD NOT FIND ON CIVIL. |
| | |
| | 4. COMPLIED |
| | |
| | 5. NOT COMPLIED SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 6.NOT COMPLIED PER FBC FG TABLE 402.4(2) AT A MBTU LOAD |
| | OF 480 AND A DISTANCE OF 30' THE FIRST SECTION OF PIPE |
| | BETWEEN THE METER AND FRYER SHALL BE 11/4 THE TWO |
| | SECTIONS OF PIPE BETWEEN THE FRYERS AND GRIDDLE SHALL |
| | BE 1" PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7.NOT COMPLIED SHOW THE SIZES OF THE BRANCH PIPING |
| | CONNECTING EACH APPLIANCE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. COMPLIED |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |