2018-12-11 15:48:132ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PREVIOUS GAS COMMENTS:
  
 1. NOT COMPLIED SHT. P5.1 UNDER THE GAS NOTES #5 IT IS
 REFERENCING A 5LB TO 1/2LB REGULATOR AT EACH APPLIANCE
 IS THIS A 5LB SYSTEM PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1 SHT WAS CHANGED TO P6.1 NOTE #6
  
 2.NOT COMPLIED PLEASE INDICATE SYSTEM PRESSURE ON THE
 RISER. PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 3.NOT COMPLIED SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER
 THE 2017 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2. SHOW METER ON
 RISER RESPONSE LETTER STATED IT WAS SHOWN ON CIVIL I
 COULD NOT FIND ON CIVIL.
  
 4. COMPLIED
  
 5. NOT COMPLIED SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6.NOT COMPLIED PER FBC FG TABLE 402.4(2) AT A MBTU LOAD
 OF 480 AND A DISTANCE OF 30' THE FIRST SECTION OF PIPE
 BETWEEN THE METER AND FRYER SHALL BE 11/4 THE TWO
 SECTIONS OF PIPE BETWEEN THE FRYERS AND GRIDDLE SHALL
 BE 1" PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 7.NOT COMPLIED SHOW THE SIZES OF THE BRANCH PIPING
 CONNECTING EACH APPLIANCE. PER WPB AMEND TO FBC 107.2.1
  
 8. COMPLIED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  