Plan Review Notes
Plan Review Notes For Permit 18060562
Permit Number 18060562
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2018-10-05 12:38:14THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 IN AN EFFORT TO MOVE THIS PROJECT FORWARD PLEASE
 CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET A 0.01 WAS NOT CORRECTED WITH THE COORECT
 EDITIONS OF THE CURRENT NFPA CODES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
 COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2014
 EDITION.
  
 PLEASE ENSURE COMPLIANCE AND UPDATE YOUR REFERNECES FOR
 FUTURE SUBMITTALS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  