Plan Review Notes
Plan Review Notes For Permit 18060562
Permit Number 18060562
Review Stop P-GREASE
Sequence Number 1
Notes
Date Text
2018-12-11 15:31:022ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. C.6 SHOWS A 750 GAL. CONCRETE GREASE
 INTERCEPTOR SHT. P5.1 SHOWS A GB2 35-50 GAL.
 INTERCEPTOR PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. THE SCHIER GB2 SHALL BE INSTALLED INDOORS ONLY. PER
 MANUFACTURE SPECIFICATIONS PLEASE CLARIFY ON PLUMBING
 FLOOR PLAN THE LOCATION.
  
 3. SHT. P5.1 THE MANUFACTURE SPECIFICATIONS SHOWN ON
 PLAN DO NOT MATCH SPECIFICATION FROM SCHIER FOR A GB2
 PLEASE CLARIFY.
  
 4. PROVIDE SIZING CALCULATIONS FROM SCHIER TO INCLUDE
 THE SINGLE COMPARTMENT SINK NEXT TO WALK IN FREEZER,
 FLOOR DRAIN, MOP SINK AND THREE COMP SINK. THE MIN SIZE
 OF THE GREASE INTERCEPTOR SHALL BE 750GAL OR A
 HYDROMACHANICAL EQUIVALENT PER WPB UTILITIES DEPT YOU
 CAN CONTACT JEFFERY ODOMS AT 822-2172 WITH QUESTIONS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  