| 2018-08-08 11:20:28 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE MOPSINK SHALL DISCHARGE THROUGH THE GREASE TRAP. |
| | PER FBC PL 1003.3.1 |
| | |
| | 2. THE FLOOR DRAINS AND THE MOP SINK SHALL BE INCLUDED |
| | IN THE GREASE TRAP SIZING CALCULATIONS. PER FBC PL |
| | 1003.3.1 |
| | |
| | 3. SHT. P2.1, P3.1 THE FLOOR PLAN SHOWS A SINK NEXT TO |
| | THE REACH IN FREEZER #007 IT DOES NOT SHOW UP ON THE |
| | ISOMETRIC DRAWINGS THE SINK SHALL CONNECT TO THE GREASE |
| | SYSTEM. PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND |
| | INSTALLATION GUIDE FOR THE GREASE TRAP. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 5. PLEASE EXPAND THE ISOMETRIC DRAWING THEY ARE TO |
| | CONGESTED TO DETERMINE CODE COMPLIANCE. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 6. PLEASE PROVIDE STORM DRAIN ISOMETRIC DRAWING |
| | INCLUDING SQFT DRAINED. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |