2018-08-08 11:20:281ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE MOPSINK SHALL DISCHARGE THROUGH THE GREASE TRAP.
 PER FBC PL 1003.3.1
  
 2. THE FLOOR DRAINS AND THE MOP SINK SHALL BE INCLUDED
 IN THE GREASE TRAP SIZING CALCULATIONS. PER FBC PL
 1003.3.1
  
 3. SHT. P2.1, P3.1 THE FLOOR PLAN SHOWS A SINK NEXT TO
 THE REACH IN FREEZER #007 IT DOES NOT SHOW UP ON THE
 ISOMETRIC DRAWINGS THE SINK SHALL CONNECT TO THE GREASE
 SYSTEM. PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION GUIDE FOR THE GREASE TRAP. PER WPB AMEND
 TO FBC 107.2.1
  
 5. PLEASE EXPAND THE ISOMETRIC DRAWING THEY ARE TO
 CONGESTED TO DETERMINE CODE COMPLIANCE. PER WPB AMEND
 TO FBC 107.2.1
  
 6. PLEASE PROVIDE STORM DRAIN ISOMETRIC DRAWING
 INCLUDING SQFT DRAINED. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  