2018-07-12 16:39:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18060562
 7/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC-17 EC.
  
 2) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOOD
 AND FIRE SUPPRESSION SYSTEM, HOWEVER THE PLANS FOR THE
 MAIN PERMIT SHALL PROVIDE THE FOLLOWING INFORMATION:
  
 A) A MEANS OF SUPPLYING MAKEUP AIR DURING THE OPERATION
 OF THE HOOD EXHAUST SYSTEM- SECTION 508.1 FBC M.
 CONCERNING THE SEQUENCE OF OPERATIONS NOTE ON SHEET
 M2.1, THE WINDOWS CANNOT BE USED AS MAKEUP AIR OPENINGS
 BECAUSE THEY ARE NOT CONSIDERED GRAVITY OPENINGS.
  
 B) EQUIPMENT SCHEDULES FOR THE HOOD, EXHAUST FAN, AND
 MAKEUP AIR UNIT.
  
 C) LOCATIONS OF THE FANS AND REQUIRED CLEARANCE
 DISTANCES- SECTIONS 401.4 AND 506.3.13 FBC M.
  
 D) AN AIR BALANCE SCHEDULE OR DIAGRAM INDICATING THE
 DESIGN OUTDOOR AIR BALANCE. THE DESIGN OUTDOOR AIR
 BALANCE SHALL INDICATE ALL EXHAUST AND REPLACEMENT AIR
 FOR THE FACILITY, PLUS THE NET EXFILTRATION IF
 APPLICABLE. THE TOTAL REPLACEMENT AIR AIRFLOW RATE
 SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE PLUS THE NET
 EXFILTRATION- SECTION 508.1.1
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 GAS-FIRED COOKING APPLIANCES- SECTION 623.1 FBC FG.
  
 4) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO THE
 COOKING APPLIANCES AND PROVIDE CALCULATIONS- SECTION
 304 FBC FG. PLEASE NOTE THAT THERE IS NO KITCHEN
 EQUIPMENT SCHEDULE ON SHEET A1.11.
  
 5) INDICATE HOW THE DRY STORAGE ROOM WILL BE VENTILATED
 AND PROVIDE A CALCULATION- SECTION 401.2.
  
 6) SHEET M2.1 & M6.1: A SPACE HEATING SYSTEM SHALL BE
 PROVIDED TO THE KITCHEN IN COMPLIANCE WITH SECTION
 309.1 FBC M. THE AC EQUIPMENT SCHEDULE INDICATES NO
 HEAT FOR THE AHU'S.
  
 7) M2.1: CLARIFY HOW THE AC SYSTEMS WILL ONLY RUN AFTER
 HOURS ONLY WHEN THE PLAN SHOWS THEY ARE BEING
 CONTROLLED THERMOSTATICALLY. PLEASE SEE SECTION
 C403.2.4- C403.2.4.2.3 FBC EC.
  
 8) M6.1: THE GH-1 (COOK 16X16 GI) IS A GRAVITY
 VENTILATOR, HOWEVER IT IS INCLUDED IN THE EXHAUST FAN
 SCHEDULE WITH AN EXHAUST RATE OF 750 CFMS.
  
 9) SUBMIT FL. PRODUCT APPROVALS OR MIAMI-DADE NOA'S FOR
 THE AC STANDS, AND THE ROOF MOUNTED EXHAUST FANS.
 PROVIDE SITE SPECIFIC ENGINEERING FOR UNIT ANCHORING
 AND ATTACHMENTS TO THE ROOF STRUCTURE- SECTION 301.15
 FBC M.
  
 10) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR
 HANDLERS- SECTION 307.2 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  