2018-08-08 11:43:031ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. SHT. P5.1 UNDER THE GAS NOTES #5 IT IS REFERENCING A
 5LB TO 1/2LB REGULATOR AT EACH APPLIANCE IS THIS A 5LB
 SYSTEM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE INDICATE SYSTEM PRESSURE ON THE RISER. PLAN
 PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 THRU 402.6 OR
 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6. PER FBC FG TABLE 402.4(2) AT A MBTU LOAD OF 480 AND
 A DISTANCE OF 30' THE FIRST SECTION OF PIPE BETWEEN THE
 METER AND FRYER SHALL BE 11/4 THE TWO SECTIONS OF PIPE
 BETWEEN THE FRYERS AND GRIDDLE SHALL BE 1" PLEASE
 CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 7. SHOW THE SIZES OF THE BRANCH PIPING CONNECTING EACH
 APPLIANCE. PER WPB AMEND TO FBC 107.2.1
  
 8. SHOW AUTOMATIC EMERGENCY SHUTOFF VALVE ON THE RISER.
 PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  