| 2018-07-26 17:13:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET A0.01 |
| | IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC |
| | PREFACE (ALSO SEE CURRENT CODES ABOVE) |
| | 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | 3. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER |
| | CODE. NEC 210.64 |
| | 4. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS |
| | IN KITCHEN/CONCESSION AREA. NEC 210.8 |
| | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 7. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING POWER |
| | ALLOWANCES PER THE FBC ENERGY CONSERVATION IN RELATION |
| | TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO COMPLY |
| | WITH CODE. FBC EC C405.5.1 |
| | 8. PROVIDE BLOCK NOTE INDICATING COMPLIANCE: ?WITHIN 30 |
| | DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD |
| | DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDE TO |
| | THE BUILDING OWNER, INCLUDING: 1. A SINGLE LINE DIAGRAM |
| | OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2. |
| | FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL |
| | DISTRIBUTION.? FBC EC C405.6.4.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |