2018-08-11 19:22:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS.
 2017 FBC-B 2204.1 WELDING
 2017 FBC B 2204.4.2 BOLTING.
  
 PLEASE ADVISE; WHO WILL BE PERFORMING THE INSPECTIONS
 FOR WELDED/BOLTED CONNECTIONS?
  
 2. SEE FIRE COMMENTS REGARDING FIRE SPRINKLERS AS THEY
 ARE APPLICABLE FOR BUILDING REVIEW.
  
  