Plan Review Notes
Plan Review Notes For Permit 18060557
Permit Number 18060557
Review Stop P
Sequence Number 2
Notes
Date Text
2018-07-24 10:57:041) SUBMIT MANUFACTURER'S SPECIFICATIONS ON THE HEAT
 PUMP. WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST.
 2) THE HEAT PUMP SHALL COMPLY WITH 2017 FBC- ENERGY
 SEC. R 403.10.5.2ND REQUEST.
 3) SUBMIT TWO COPIES OF AN ENLARGED POOL PUMP CURVE.
 THE PRINTING IS ILLEGIBLE ON THE ONE ON THE PLANS.
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS.2ND REQUEST.
 4) THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW
 THE FRICTION LOSS THROUGH ALL THE SYSTEM CCOMPONENTS.
 THE CALCULATOR SHOWS THE PIPE, FITTINGS, VALVES,
 HEATER, FILTER, ETC. BUT THERE IS NO FRICTION LOSS
 ASSOCIATED WITH THESE ITEMS.CLARIFY. PLEASE IDENTIFY
 THE SOURCE OF THE TDH CALCULATOR FOR VERIFICATION OF
 THE TDH.
 5) SHT. 4 OF 4 - GENERAL NOTES SHEET - VARIOUS NOTES
 REFER TO APSP 7 - 2006 EDITION. THE 2017 FBC REFERENCES
 THE 2013 EDITION. REVISE ALL NOTES TO REFLECT THE 2013
 EDITION. 2ND REQUEST.
 6) VOID OUT OLD PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  