| Plan Review Notes For Permit 18060557 |
| Permit Number |
18060557 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-28 06:54:04 | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS ON THE HEAT | | | PUMP. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) THE HEAT PUMP SHALL COMPLY WITH 2017 FBC- ENERGY | | | SEC. R 403.10.5. | | | 3) IS THE POOL EQUIPPED WITH AN AUTO-FILL? CLARIFY ON | | | THE PLANS. | | | 4) SUBMIT TWO COPIES OF THE AN ENLARGED POOL PUMP | | | CURVE. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS | | | SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS | | | IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE | | | TDH CALCULATIONS. | | | 5) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE | | | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM | | | ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN | | | DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC | | | 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION | | | ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT | | | REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED | | | THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET | | | FITTING ASSEMBLY (DRAIN COVER). REVISE SHT. 2 OF 4. | | | 6) SHT. 4 OF 4 - GENERAL NOTES SHEET - VARIOUS NOTES | | | REFER TO APSP 7 - 2006 EDITION. THE 2017 FBC REFERENCES | | | THE 2013 EDITION. REVISE ALL NOTES TO REFLECT THE 2013 | | | EDITION. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|