| 2018-06-27 14:42:11 | 06/27/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | I HAVE PUT IN YOUR PACKAGE A GAS ISOMETIC FROM 2007 FOR |
| | YOUR REFFREANCE ON THE OLD GAS SYSTEM THAT WAS IN THE |
| | CITY RECAORD, PLEASE USE THESE FOR REFFREANCE ONLY, |
| | THEY WILL BE TURNED DOWN IF USED AS RE SUBMITALS. |
| | |
| | 1. PLEASE LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL |
| | GAS RES. SEC. G2420.4. |
| | 2. IT APPREARS THE AN EXSISTING GAS AND APPLIANCE ARE |
| | IN A PREVIOUS GAS SYSTEM, PLEAE LIST THE BTU LOAD OF |
| | EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| | REFER TO THE 2017 FBC FUEL GAS SECS. 401.8 THROUGH |
| | 402.6.1 AND TABLES 402.4 (1) THROUGH 402.4 (37) OR 2017 |
| | FBC FUEL GAS RES. SEC. G2413. |
| | 3. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. IF THIS IS A NEW METER, PLEASE INDICATE THE |
| | DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN PER |
| | 2017 FBC FUEL GAS RES. SEC. G2413.2 |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2017 FBC FUEL GAS RES. SEC. G2421.1. |
| | 5. NEED TO SHOW SHUTOFF VALVE ON GAS, 2017 FBC FUEL GAS |
| | RES. SEC. 404.15, 411. |
| | 6. THE COPY OF THE TABLE 402.4(22) THIS FROM AN |
| | OUTDATED FUEL GAS CODE. THE FUEL GAS CODE IN EFFECT IS |
| | THE 2017 FBC FUEL GAS. SUBMIT TWO COPIES OF THE CORRECT |
| | SIZING TABLE. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| | 7. PLEASE SUBMIT TWO COPIES OF TABLES OF ALL GAS PIPING |
| | MATERIAL BEING INSTALLED, ALL PIPE SIZES, AND THE |
| | CORRESPONDING EHD NUMBER OF THE CORRUGATED STAINLESS |
| | STEEL TUBING (IF APPLICABLE) FOR EACH PIPE SIZE. WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 8. YOUR TANK SHOW TO BE MIN OF 10' FROM ANY DOOR OR |
| | SCREENED WINDOW AND 4? HIGH FENCE ACCORDING TO |
| | MANUFACTURES INSTALATION MANUAL WHICH WAS NOT |
| | SUBMITTED, ZOING HAS ISSUES WITH YOUR LOCATION SO |
| | PLEASE PROVIDE SPEC ON YOUR NEXT REVIEW AND HAVE ON |
| | SITE FOR FIELD VERIFICATION OF FINAL INSPECTION. WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |