Plan Review Notes
Plan Review Notes For Permit 18060545
Permit Number 18060545
Review Stop G
Sequence Number 1
Notes
Date Text
2018-06-27 14:42:1106/27/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 I HAVE PUT IN YOUR PACKAGE A GAS ISOMETIC FROM 2007 FOR
 YOUR REFFREANCE ON THE OLD GAS SYSTEM THAT WAS IN THE
 CITY RECAORD, PLEASE USE THESE FOR REFFREANCE ONLY,
 THEY WILL BE TURNED DOWN IF USED AS RE SUBMITALS.
  
 1. PLEASE LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL
 GAS RES. SEC. G2420.4.
 2. IT APPREARS THE AN EXSISTING GAS AND APPLIANCE ARE
 IN A PREVIOUS GAS SYSTEM, PLEAE LIST THE BTU LOAD OF
 EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM.
 REFER TO THE 2017 FBC FUEL GAS SECS. 401.8 THROUGH
 402.6.1 AND TABLES 402.4 (1) THROUGH 402.4 (37) OR 2017
 FBC FUEL GAS RES. SEC. G2413.
 3. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. IF THIS IS A NEW METER, PLEASE INDICATE THE
 DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN PER
 2017 FBC FUEL GAS RES. SEC. G2413.2
 4. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS RES. SEC. G2421.1.
 5. NEED TO SHOW SHUTOFF VALVE ON GAS, 2017 FBC FUEL GAS
 RES. SEC. 404.15, 411.
 6. THE COPY OF THE TABLE 402.4(22) THIS FROM AN
 OUTDATED FUEL GAS CODE. THE FUEL GAS CODE IN EFFECT IS
 THE 2017 FBC FUEL GAS. SUBMIT TWO COPIES OF THE CORRECT
 SIZING TABLE. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 7. PLEASE SUBMIT TWO COPIES OF TABLES OF ALL GAS PIPING
 MATERIAL BEING INSTALLED, ALL PIPE SIZES, AND THE
 CORRESPONDING EHD NUMBER OF THE CORRUGATED STAINLESS
 STEEL TUBING (IF APPLICABLE) FOR EACH PIPE SIZE. WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 8. YOUR TANK SHOW TO BE MIN OF 10' FROM ANY DOOR OR
 SCREENED WINDOW AND 4? HIGH FENCE ACCORDING TO
 MANUFACTURES INSTALATION MANUAL WHICH WAS NOT
 SUBMITTED, ZOING HAS ISSUES WITH YOUR LOCATION SO
 PLEASE PROVIDE SPEC ON YOUR NEXT REVIEW AND HAVE ON
 SITE FOR FIELD VERIFICATION OF FINAL INSPECTION. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  